Nominal current for discharge screw
Nominal current of the suction screw motor according to
the identification plate on the motor.
During troubleshooting of suction screw, this turns
backwards for
Duration, how long should the suction screw turn
backwards during troubleshooting.
During troubleshooting of suction screw, this turns
forwards for
Duration, how long should the suction screw turn forwards
during troubleshooting.
Minimum current monitoring active
▪ YES: A failure of measured phase is detected.
Service hours of suction screw
Prerequisite: Large-scale suction system with one cyclone
and 2 rotary valves.
operating hours of suction screw discharge on a GASS.
Suction turbine operating hours
Counter for the operating hours of the suction turbine.
Preliminary suction time
Time before the discharge screw starts.
Suction zone 1 … 3 activated
A suction zone can be activated or deactivated.
Deactivated suction zones are skipped when changing the
suction zones.
Screw cycle
Discharge screw runtime, minus an adjustable pause time.
Screw at address
Address at which the screw has been connected.
Parameters overview
4
Feed system
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en