4.5.5 Boiler - General settings
System menu
Boiler
Modem installed
▪ NO: The boiler does not have a modem for data
transfer installed.
▪ YES: The boiler has a modem for data transfer
installed.
Memory cycle of data logger
If the boiler is equipped with a data logger the most
important boiler data is stored on a SD card. This
parameter specifies at what intervals the recording should
be started.
Output warnings through fault message relays
▪ NO: When there is an “error” or “alarm” the common
fault relay closes.
▪ YES: In addition to an “error” or “alarm”, the common
fault relay closes when a “warning” is present on the
boiler.
Which temperature scale should be used
▪ Celsius (°C): Displayed temperature values and settings
are shown in °C.
▪ Fahrenheit (°F): Displayed temperature values and
settings are shown in °F.
Always log data in °C
▪ YES: In conjunction with a data logger, all temperature
values are saved in °C.
▪ NO: In conjunction with a data logger, all temperature
values are saved in °F.
Send a line break when ASCII data output on COM2
▪ NO: When a new data set is issued it will be added to
the previous one.
▪ YES: A line break for better visualisation is sent
between the individual data sets.
Reset counter since last maintenance
▪ NO: The service hours counter since last maintenance
continues to run.
▪ YES: The service hours counter since last maintenance
is set to “0”.
Source for ext. power demand (0 - off, 1 - 0-10V, 2 -
Modbus)
Defines whether the boiler is controlled via an external
power demand. If “1 - 0-10V” or “2 - Modbus” is selected
as the source, the boiler release and output can be
controlled via an adjustable input at the analogue module
(0-10V) or via the modbus.
⇨ See "External power demand" [page 26]
Invert ext. power demand via analogue input
Designed to invert the input signal (0V = 0% ➾ 0V =
100%).
Input external power demand
Current input value for the external power demand.
Current external power demand
Current effective specified value for the boiler taking the
minimum times into consideration.
Adopt specified material values
YES: The preset boiler parameters for the chosen fuel
selection are adopted. When the process is completed the
parameter changes back to “NO”.
Adopt specified boiler values
YES: The preset boiler parameters for the selected boiler
type are adopted. When the process is completed the
parameter changes back to “NO”.
Adopt standard settings (all values are reset)
▪ YES: Adopting standard factory settings. This resets all
parameters! Once the settings have been applied, the
parameter automatically switches to “NO” and the boiler
must be reset, otherwise, boiler function is no longer
guaranteed.
EEPROM reset
▪ YES: All boiler settings and system configurations are
deleted. The boiler is only functional again once it has
been recommissioned by Froling customer services or
authorized installer.
Parameters overview
4
Boiler
Service manual Lambdatronic H 3200 for wood chip boiler | B1480721_en
67