9-2
4) Use shield wires to connect the output lines to the motor. Use as short wires as possible.
Connect the earth to the earth terminals on both the motor and the inverter.
Electrically connect the shield wires such that the shield of the shield wires completely fills the periphery of the
holes at the entrance to the control panel.
5) If a ferrite ring is provided, make sure the wire pass through the ferrite ring. Wiring depends on the type of your
inverter, and follow the Figure 9-8, 9-9, or 9-10 to wire.
6) Use a shield wire to wire to the control terminals on your inverter. Make sure that the shield of the shield wire is
connected to earth. Use as short wires as possible for all places. Separate the wiring from the power supply to
the filter and that from the inverter to the motor as far as possible.
Summary of Contents for 5000VG7S Series
Page 7: ...0 6 Warning Label Position for Inside the Inverter...
Page 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...
Page 36: ...2 18 l Control circuit terminals Control circuit terminals Screw size M3...
Page 94: ...9 4 FS5941 40 47 Figure 9 1 FS5941 60 52 FS5941 86 52 Figure 9 2...
Page 96: ...9 6 RF3280 F11 RF3400 F11 Figure 9 5 RF3880 F11 Figure 9 6 6 6 Figure 9 7 F200160...