5-10
Communication
address
Fcode
485
number
Link number
Function name
Setting range
a26
51Ah
( h) M2-R2
correction
coefficient 3
0.010 to 5.000
a27
51Bh
( h) M2-Exciting
current
correction
coefficient
0.000 to 5.000
a28
51Ch
( h) M2-ACR-P
gain
0.1 to 1.0 to 20.0
a29
51Dh
( h) M2-ACR-I gain 0.5 to 1.0 to 100.0 ms
a30
51Eh
( h) M2-PG pulses 100 to 1024 to 60000
a31
51Fh
( h) M2-thermistor
selection
0 to 1 to 3
0 : No use thermistor
1 : NTC thermistor
2 : PTC thermistor
3 : Ai (M-TMP)
Please do the protection level setting of the motor at
E30-E32.
a32
520h
( h) M2-Electronic
thermal
overload relay
(Selection)
0 to 2
The motor overheating protection operates by using
NTC thermistor with the motor only for VG. In this
case, please make setting a Electronic thermal
"Inactive".
0 : Inactive
1 : Active (for standard motor, self-cooling fan)
2 : Active (for inverter motor, separate cooling fan)
a33
521h
( h) M2-Electronic
thermal
overload relay
(Level)
0.01 to 99.99A
100.0 to 999.9A
1000 to 2000A
a34
522h
( h) M2-Electronic
thermal
overload relay
(Thermal time
constant)
0.5 to 75.0 min
a35
523h 229( E5 h) M3-Rated
capacity
0.00 to 500.00kW at F60=0
0.00 to 600.00HP at F60=1
a36
524h 230( E6 h) M3-Rated
current
0.01 to 99.99A
100.0 to 999.9A
1000 to 2000A
a37
525h 231( E7 h) M3-Rated
voltage
80 to 999 V
a38
526h 232( E8 h) M3-Maximum
voltage
80 to 999 V
a39
527h 233( E9 h) M3-Rated
speed
50 to 1500 to 24000 r/min
(Target ROM No. H1/20012 or later)
a40
528h 234( EA h) M3-Maximum
speed
50 to 1500 to 24000 r/min
(Target ROM No. H1/20012 or later)
a41
529h 235( EB h) M3-Poles
2 to 4 to 12 (poles)
a42
52Ah 236( EC h) M3-%R1
0.00 to 30.00 %
a43
52Bh 237( ED h) M3-%X
0.00 to 50.00 %
a44
52Ch 238( EE h) M3-Exciting
current
0.01 to 99.99A
100.0 to 999.9A
1000 to 2000A
a45
52Dh 239( EF h) M3-Slip
compensation
control
-20.000 to 0.000 to 5.000 Hz
a46
52Eh 240( F0 h) M3-Torque
boost
0.0 to 20.0
0.0 : Automatic torque boost (for CT load)
0.1 to 0.9 : Manual torque boost (for Square torque
load)
1.0 to 1.9 : Manual torque boost (for VT load)
2.0 to 20.0 : Manual torque boost (for CT load)
a47
52Fh 241( F1 h) M3-Thermistor
selection
0 to 1 to 3
0 : No use thermistor
1 : NTC thermistor
2 : PTC thermistor
3 : Ai (M-TMP)
Please do the protection level setting of the motor at
E30-E32.
a48
530h 242( F2 h) M3-Electronic
thermal
overload relay
(Selection)
0 to 2
0 : Inactive (when using PTC thermistor)
1 : Active (for standard motor, self-cooling fan)
2 : Active (for inverter motor, separate-cooling fan)
a49
531h 243( F3 h) M3-Electronic
thermal
overload relay
(Level)
0.01 to 99.99A
100.0 to 999.9A
1000 to 2000A
a50
532h 244( F4 h) M3-Electronic
thermal
overload relay
(Thermal time
constant)
0.5 to 75.0 min
O: Optional Functions
Communication
address
Fcode
485
number
Link number
Function name
Setting range
o01
601h 245( F5 h) DIA function
select
0 to 1
0 : Binary
1 : BCD
o02
602h 246( F6 h) DIB function
select
0 to 1
0 : Binary
1 : BCD
o03
603h
( h) DIA BCD input
speed setting
99 to 1000 to 7999
o04
604h
( h) DIB BCD input
speed setting
99 to 1000 to 7999
o05
605h
( h) Pulse
feedback
select
0 to 1
0 : Build-in PG
1 : PG(PD) option
o06
606h
( h) Line speed
detection
(digital) (PG
pulses)
100 to 1024 to 60000 (P/R)
o07
607h
( h) Line speed
detection
(digital) (Pulse
correction
function 1)
0 to 1000 to 9999
o08
608h
( h) Line speed
detection
(digital) (Pulse
correction
function 2)
0 to 1000 to 9999
o09
609h
( h) Definition of
absolute PG
signal input
0 to 16
o10
60Ah
( h) Magnetic pole
position offset
0000 to FFFF
o11
60Bh
( h) Salient pole
ratio
1.000 to 3.000
o12
60Ch
( h) Pulse
reference
select
0 to 2
0 : PG(PR) option
1 : Internal input
o13
60Dh
( h) Pulse train
input form
selection
0 to 2
0 : Phase difference 90° between A-phase and B-phase
1 : A-phase : Reference pulse, B-phase : Reference
sign
2 : A-phase : Forward pulse, B-phase : Reverse pulse
o14
60Eh 247( F7 h) Reference
pulse
correction 1
0 to 1000 to 9999
o15
60Fh 248( F8 h) Reference
pulse
correction 2
0 to 1000 to 9999
o16
610h 249( F9 h) APR P-gain
0.0 to 1.0 to 999.9 (times)
o17
611h 250( FA h) Feed forward
gain
0.0 to 1.5 (times)
o18
612h
( h) Deviation over
width
0 to 65535 (pulse)
o19
613h
( h) Deviation zero
width
0 to 20 to 1000 (pulse)
o30
61Eh
( h) Action on
communica-
tion error
0 to 3
0: Forced stop
1: Stops after preset operation time.
2: Stops if transmission error continues longer than the
operation time.
3 : Continuous operation.
o31
61Fh
( h) LINK error
(Timer)
0.01 to 0.10 to 20.00 s
o32
620h
( h) LINK format
select
0 to 1
0 : 4W + 4W
1 : 8W + 8W
o33
621h 253( FD h) Multi-winding
motor system
(mode)
0 to 1
0 : Inactive
1 : Active
o34
622h
( h) Multi-winding
motor system
(Slave station
number)
1 to 5
The numbers of slave units except master unit are set
when multi-winding motor system is effective.
o35
623h
( h) Link station
address
0 to 255
o36
624h
( h) Link system
slave station
0 to 1 to 155
(Target ROM No. H1/20062 or later)
o37
625h
( h) Communica-
tion definition
setting
00 to 10 to 24
o38
626h
( h) UPAC
(Start/stop)
0 to 2
0 : Stop UPAC
1 : Start UPAC
2 : Start UPAC (Initialized start)
Definition whether the instruction data from UPAC
option is made active or inactive.
Underline indicates a factory setting.
Items without underline have different factory settings according to capacity.
You can change the setting of a function indicated by during operation.
You should stop operation to change the setting of other functions.
Summary of Contents for 5000VG7S Series
Page 7: ...0 6 Warning Label Position for Inside the Inverter...
Page 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...
Page 36: ...2 18 l Control circuit terminals Control circuit terminals Screw size M3...
Page 94: ...9 4 FS5941 40 47 Figure 9 1 FS5941 60 52 FS5941 86 52 Figure 9 2...
Page 96: ...9 6 RF3280 F11 RF3400 F11 Figure 9 5 RF3880 F11 Figure 9 6 6 6 Figure 9 7 F200160...