2-1
2. Installation and Connection
2-1 Operating Conditions
Install the product under the conditions specified in Table 2-1-1.
Table 2-1-1 Operating Conditions
Item
Requirement
Place
Indoor
Ambient
temperature
-
10 to +50°C
Relative humidity
5% to 95% (no condensation allowed)
Atmosphere
The product should not be exposed to dust, direct
sunlight, corrosive gas, oil mist, vapor, waterdrops, or
air containing much salt.
No condensation should occur due to sudden
temperature changes.
Altitude
1,000m or less (if more than 1,000m, see Table 2-1-
2)
2 to 9Hz: 3mm amplitude
9 to 20Hz: 9.8m/s
2
(or 2m/s
2
for 200V, 75kW or
higher and 400V, 90kW or higher inverters)
Vibration
20 to 55Hz: 2m/s
2
55 to 200Hz: 1m/s
2
Table 2-1-2 Output Reduction Rates at Higher Altitudes
Altitude
Output Current Reduction Rate
1,000m or less
1.00
1,000-1,500m
0.97
1,500-2,000m
0.95
2,000-2,500m
0.91
2,500-3,000m
0.88
Summary of Contents for 5000VG7S Series
Page 7: ...0 6 Warning Label Position for Inside the Inverter...
Page 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...
Page 36: ...2 18 l Control circuit terminals Control circuit terminals Screw size M3...
Page 94: ...9 4 FS5941 40 47 Figure 9 1 FS5941 60 52 FS5941 86 52 Figure 9 2...
Page 96: ...9 6 RF3280 F11 RF3400 F11 Figure 9 5 RF3880 F11 Figure 9 6 6 6 Figure 9 7 F200160...