Figure 16
Set Up with Tool Suite (cont.)
FGRIO Master
(9)IO Settings Tab– (cont.)
Time Out
– 0-255. This setting determines the amount of time to wait before issuing a Link
Alarm due to loss of communication between the FGRIO Master and IO Slave.
A setting of 1 = 1/6 second
6 = 1 second
42 = 7 seconds
252 = 42 seconds
Sensor Power
– Always On or Gated. A setting of Always On supplies continuous power to
the sensor at the IO Slave. A setting of Gated, is used when the RTU provides a switched
power output to control powering the sensors at the IO Slave and analog outputs of the
FGRIO Master on and off.