Q: 

Can data be sent directly from the IO Slave to the Master of the FreeWave network? 

 

A: 

No.  The FGRIO system functions as wire replacement only.  The IO Slave does not  

     have the capability of transmitting data directly to the Master of the network. 

 
 
Q: 

What are the sizes of the FGRIO Master and Slave? 

 

A: 

The board level IO Slave has the same footprint as the FGRO9 family.  The board level IO 

     Slave dimensions are 127 mm (L) x 61 mm (W) x 15.5 mm (H).  The FGRIO Master is a  
     standard footprint FGRO9 plus an IO Interface board on top, differing only in width at 2.75 
     inches.  The dimensions of the FGRIO Master are 140 mm (L) x 70 mm (W) x 34 mm (H). 
 
 

Q: 

What timing issues does IO introduce? 

 

A: 

Although IO mimics a wired connection, the electronics and communication heartbeat 

     do cause some signal delay.  The  worst case delay for digital signals in either direction and  
     the Sensor Power command from FGRIO Master to IO Slave is 167 msec, assuming a  
     robust link.  Worst case delay from FGRIO Master Sensor Power assertion to FGRIO Master 
     Analog Output refresh is 700 msec. 
 

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-20028-FreeWave-FGR2-IO-IOE-Radio-Enclosed-900-MHz-I/O-Slave-Radio.aspx

Summary of Contents for FGR2-IOS-CE-U

Page 1: ...ual Version 1 FGRIO Master FGRIO M FGRIO Slave FGRIO S FGR2 IO Slave FGR2 IOS CE U RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 20028 FreeWave FGR2 IO IOE Radio Enclosed 900 MHz...

Page 2: ...plosion Hazard Substitution of components may impair suitability for Class I Division 2 The diagnostics port and cable do not have a latching connector and cannot be used in a hazardous location RSPSu...

Page 3: ...Book 14 Radio Transmission Characteristics 14 15 Max and Min Packet Sizes 14 15 RF Data Rate 15 Retry Timeout 15 Multipoint Parameters 15 Number of Repeaters 15 Network ID 15 FGRIO Setup 16 17 Set Up...

Page 4: ...and Digital Def 2 25 Default Delay 25 Digital Input Pull Up Down 25 Installation 26 34 IO Slave 26 32 B 26 1 5 Volt Sensor 26 27 4 20 Milliamp Sensor 27 28 1 5 Volt Sensor Analog Input 3 or Analog In...

Page 5: ...23 Sensor Power 33 34 Link Alarms 34 Frequently Asked Questions 34 35 Wiring Diagram 36 Specifications 27 39 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 20028 FreeWave FGR2 IO...

Page 6: ...te as a Slave Repeater in the SCADA system FGRIO Slave FreeWave wireless radio transceiver that accepts up to a total of 4 input signals from sensors then transmits these signals over air to the FGRIO...

Page 7: ...es exist only at one of a set of discrete levels all transitions between levels being ignored The states of a digital circuit are often referred to as on or off high or low VSNS This is screw terminal...

Page 8: ...Input 3 Digital Input 4 Analog Output 1 Analog Output 2 Analog Output 3 Analog Output 4 Digital Output 1 Digital Output 2 Digital Output 3 Digital Output 4 Link Alarm CMD Alarm Not Used Sensor Power D...

Page 9: ...nalog Input 4 1 Digital Input 1 OR Analog Input 3 12 Ground 11 B IN 10 Analog Input 2 9 Ground 8 Analog Input 1 7 VSNS Analog Out 1 6 Ground 5 Digital Output 2 4 Digital Output 1 3 Ground 2 Digital In...

Page 10: ...RIO Slave Carrier Detect CD Transmit TX Clear to Send CTS Carrier De tect CD Transmit TX Clear to Send CTS Solid green bright Solid red dim FLICKERING red Blinking green Blinking red Blinking red The...

Page 11: ...nd IO radios in the Network 6 Network ID In addition to entering the IO Slaves serial numbers in the Call Book the Network ID being used for the Network must be set from 1 4095 Do NOT use 255 Programm...

Page 12: ...IO Master 9 FGRIO Setup Outputs on the FGRIO Master are mapped to inputs on the IO Slave Fig 7 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 20028 FreeWave FGR2 IO IOE Radio Encl...

Page 13: ...ter s output you would like to connect to the input from the Slave At the flashing curser enter the number to the left of the selected output Next enter the number found in step 3 This num ber should...

Page 14: ...s A Sensor Power 0 or 1 A setting of 0 supplies continuous power to the sensor at the IO Slave A setting of 1 Gated is used when the RTU provides a switched power output to control powering the sensor...

Page 15: ...st be set to the same ID as the rest of the network Programming both the Call Book and Network ID set tings is unique only to the FGRIO System and must be done for both integrated and stand alone appl...

Page 16: ...Point Parameters 0 Number Repeaters This setting must be set to 1 for all FGR and IO radios in the Network 6 Network ID In addition to entering the FGRIO Master s serial number in the Call Book the Ne...

Page 17: ...N Conducting to GND 2 Amps max 1 Open Drain output OFF Non Conducting 2 Make no change in state Note If programming a DO to turn on after loss of link ensure that the energized device can sustain the...

Page 18: ...Fig 12 Set Up with HyperTerminal cont 9 FGRIO Setup cont RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 20028 FreeWave FGR2 IO IOE Radio Enclosed 900 MHz I O Slave Radio aspx...

Page 19: ...stem is being inte grated into an FGR FreeWave Network The IO functionality is turned on under the IO Set tings tab Note Setting E FGRIO Master should only be selected when the FGRIO System is operati...

Page 20: ...ab Figure 15 Number Repeaters This setting must be set to 1 for all FGR and FGRIO radios in the Network Network ID In addition to entering the serial numbers of the IO Slaves in the Call Book the Netw...

Page 21: ...O M the FGRIO M outputs are mapped to the IO Slave inputs To map select the appropriate Slave input from the drop down box next to the master s output Note The slaves are labeled by their position in...

Page 22: ...6 1 second 42 7 seconds 252 42 seconds Sensor Power Always On or Gated A setting of Always On supplies continuous power to the sensor at the IO Slave A setting of Gated is used when the RTU provides...

Page 23: ...th integrated and stand alone applications Figure 17 Set Up with Tool Suite cont IO Slave In order for the FGRIO System to function properly the following settings must be programmed For all other set...

Page 24: ...reduced when going from autonomous mode to connecting back to the FGR Network If the Network Master goes down the IO Master and Slave will continue to operate in autonomous mode When the Network Maste...

Page 25: ...rial number in the Call Book the Network ID being used for the Network must be set from 1 4095 Do NOT use 255 Programming both the Call Book and Network ID settings is unique to the FGRIO System and m...

Page 26: ...DO to turn on after loss of link ensure that the energized device can sustain the state undamaged in case the loss in lengthy Default Delay This value is set in 28 second units This sets the time dura...

Page 27: ...red to the IO Slave with a 3 wire connection The Sensor Ground Wire can be connected to Ground Screw Terminal 3 9 or 12 on the terminal block of the IO Slave The Sensor Power Wire is connected to the...

Page 28: ...S screw terminal 7 on the terminal block of the IO Slave Sensor Output Low Wire is connected to the same Analog Input as the resistor on the terminal block of the IO Slave Example of one 4 20 milliamp...

Page 29: ...at screw terminal 1 and screw terminal 2 are directly usable with signals only from 1V to 2 812V in wire replacement mode Input loading can be selected as 10Kohm to GND or unloaded 1Megohm Accuracy is...

Page 30: ...typical transducer outputs so the input must be restricted For signal replication it is assumed the input signal level will be halved and the measured value sent to the FGRIO M doubled to achieve an...

Page 31: ...w terminal 7 is designed to drive only two 4 20mA transmitters to full scale If a system will use more than two the additional transmitters must be powered from a separate supply such as directly from...

Page 32: ...t 4 4 20 Milliamp Sensor Analog Input 3 or Analog Input 4 Figure 25 Figure 26 RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 20028 FreeWave FGR2 IO IOE Radio Enclosed 900 MHz I O...

Page 33: ...ng for Digital Output is 2 amps or less The Digital Output will self protect if a current of more than 2 1 2 amps is drawn and automatically retry at 16 second intervals If power on the Solenoid end d...

Page 34: ...the RTU NOTE The Digital Output actively drives Low 4V and High 4 0V Remove any RTU input pull up resistor if less than 10 K ohms Verify that signal levels meet the RTU input requirements after conne...

Page 35: ...maller wire is required for 2 wires or wire resistor into the same screw terminal Frequently Asked Questions Q Can IO be used with a 1 watt radio A The FGRIO Master operates as a standard FGR 1 watt r...

Page 36: ...t FGRO9 plus an IO Interface board on top differing only in width at 2 75 inches The dimensions of the FGRIO Master are 140 mm L x 70 mm W x 34 mm H Q What timing issues does IO introduce A Although I...

Page 37: ...e connected if available RTU Analog Output wire connects from Analog Output 1 screw terminal to Analog Input of the RTU Terminal Block of FGRIO Master Ground wire connects from Ground screw termi nal...

Page 38: ...ous Operating environment 40 C 75 C 0 to 95 humidity non condensing Specification Frequency 902 to 928 MHz Transmit Output Power FGRIO M 5 mW to 1 W 30 dBm FGRIO S 100 mW 20 dBm FRG2 IOS 5mW to 1W 30...

Page 39: ...29B DGR09RAS Analog Signals Number of Signals FGRIO S or FGR2 IOS up to 4 Inputs FGRIO M 4 Outputs 1 to 4 S per M Analog Input Range Resistance Bandwidth Analog Input 1 and 2 0 5 625V 94Kohms 67Hz Low...