www.flowair.com
| 25
Cube units are built on self-supporting frame, which should be installed on brackets or frames connected to the roof, according to
construction law in specific country and must be ousted from roof slope to a height determined by this law. The manufacturer
determines unit’s installation on the unit’s contour in accordance with frame dimensions listed below. Installing on a supported
frame on two longer sides of unit’s frame.
Cube 120 / 160 R
demonstrative solution
Cube R8
demonstrative solution
•
Unit should be mounted to a frame in such way to ensure no move of unit. Using rubber pads between unit and frame
is highly advisable.
•
Install unit in such way that inlet and exhaust are not directed to windward.
•
The manufacturer allows installation on a frame with support on the two long sides of the unit's frame.
A [mm]
internal dim. 2980
B [mm]
internal dim. 2180
C [mm]
1220
D [mm]
1220
A [mm]
Internal dim. 2180
B [mm]
Internal dim. 1260