www.flowair.com
| 23
Cube units are built on self-supporting frame, which should be installed on brackets or frames connected to the roof, according to
construction law in specific country and must be ousted from roof slope to a height determined by this law. The manufacturer
determines unit’s installation on the unit’s contour in accordance with frame dimensions listed below. Installing on a supported
frame on two longer sides of unit’s frame.
Cube 40 NWL
demonstrative solution
* Please observe the maximum dimenssons of the frame. Longer frame then specified above will result in damaging
the module.
Cube 50 / Cube 60 / Cube 80 / Cube 100
demonstrative solution
•
Unit should be mounted to a frame in such way to ensure no move of unit. Using rubber pads between unit and frame
is highly advisable.
•
Install unit in such way that inlet and exhaust are not directed to windward.
•
The manufacturer allows installation on a frame with support on the two long sides of the unit's frame.
A1 [mm]
max. 1400 *
A2 [mm]
min. 1200
B1 [mm]
max. 1400 *
B2 [mm]
min. 1200
A [mm]
internal dim. 2980
B [mm]
internal dim. 2180