8. CONTROL SYSTEM | AUTOMATYKA | STEUERUNG| АВТОМАТИКА
8.2. OPERATION
SUMMER
HALF
(13,5kW)
FULL
(27kW)
OFF
Swit
c
h
ON
ON
ON
ON
→ OFF
I
II
All
Outlet air temperature
Same as room temperature
Δt* = +15
o
C
Δt* = +25
o
C
–
Heating rods
OFF
3 heating rods active. Switched off after
reaching temperature
6 heating rods active. Switched off after
reaching temperature
OFF
Fan
Active (switch have to be set to
30
o
C)
Active while rods on. After switching rods off, the fan continues to operate for
2 minutes to cool them down.
Active for 2 minutes
*At air inlet temperature 0
o
C
Room thermostat
1. Operation mode switch
2. ON/OFF switch
3. Temperature knob
The room thermostat should to be
mounted at about 1.5m above the floor in a
well ventilated place. Do not mount near
heat sources, lights, windows and doors.
The thermostat is equipped with a 5
meters cable 7x1mm
2
. If a longer cable
needed use the same type.