3.4.1.2.
Wiring Information
The wires used for the installation of the cascading kit must have the following characteristics:
The conductors must be rated at 90 °C or more.
The conductors must be rated at 300 V or more.
Use copper or aluminum conductors OR use copper, copper-clad aluminum, or aluminum conductors
for terminals evaluated for either copper or aluminum wiring.
3.4.1.3.
Wire Connection
The stickers placed on the cascading kit provide connection information.
The table below shows information for the input wire:
Wire Range
Torque
(2) 4/0-3 AWG
150 LB-IN [17 N-M]
(2) 4 AWG
100 LB-IN [11.3 N-M]
(2) 6 AWG
80 LB-IN [9 N-M]
The table below shows information for the breaker outputs:
Wire Range
Torque
14-10 AWG
35 LB-IN
[4.0 N-M]
8 AWG
40 LB-IN
[4.5 N-M]
6-4 AWG
45 LB-IN
[5.1 N-M]
3-1/0 AWG
50 LB-IN
[5.7 N-M]