ROFINET
I
NTERFACE
FAD-40PN instruments are state-of-the-art strain gauge load cell signal digitizers with Profinet interface. These
instruments are used for any type of process weighing and force measurement including tank and silo
weighing, dynamic weighing, check weighing, filling, tension /compression force measurement etc.
The GSDML file is available on a CD which is supplied together with the instrument and unter www.flintec.com.
7.1. Front View of FAD-40PN
There are 6 status LEDs on the front panel which indicate the operational instrument status (Refer to table
8.1).and the Profinet status. The setup switch on front panel of the instrument is used for Profinet addressing
without PC (Refer to chapter 5.6) and for diagnostics (Refer to chapter 12).
When the error LED is ON, the other two LED indicate the error type (Refer to chapter 11 for details).
Load cell connection, Profinet connection, power supply and serial interface terminals are located at the front of
the DIN rail mount instrument (See figure 8.1).
Status LEDs
MS Module Status LED
Digital I/O Connector
Profinet Connector P2
Link / Activity LED
Profinet Connector
NS Network Status LED
Load Cell Connector
Setup Switch
Power Supply Terminal
RS-232C Terminal
Figure 8.1
– Front view
The meanings of these LEDs in operation are described below.
LED
Operational Mode
Symbol
Name
Weight / Force
Count
Stable
Stable
Unstable
Off for 0.3 seconds in 2 seconds
period (No stable indication)
Centre
of Zero
in the center of zero range
(-0.25 e < w < 0.25 e)
Out of center of zero range
Always off
(No center of zero indication)
Err
Error
( * )
ADC conversion error
Digital processing error
No error
ADC conversion error
Digital processing error
No error
Off
On
Flashing Off for 0.3 seconds
( * ) : Refer to the error table in chapter 11.
Table 8.1
– Status LEDs
MS Module Status LED