FAD-40 Technical Manual, Rev.2.1.0; February 2022
Page 20 of 55
4.7. Bus Addressing via Setup Switch
The bus addressing of FAD-40 instruments is done by the xFace software (Refer to chapter 5.3.1). The
alternative way for addressing is the setup switch on the front panel for addresses between 0 and 7 for RS-485,
Modbus RTU, Profibus and CANopen interfaces. This feature gives you the practical advantage for addressing
the instrument up to address 7 without requiring a PC connection.
For addressing via the setup switch, press this switch for 5 seconds. Then the status LEDs indicate the bus
address as shown in the table below. If the address is higher than 7 all LEDs are flashing. The address can be
changed by pressing the setup switch sequentially. To save and exit, press the setup switch for 5 seconds. To
return to normal operation without saving, wait 15 seconds without pressing the switch.
Err
Address Number
0 (No address)
Table 5.2
–
Bus Addressing via
Setup Switch
1
2
3
4
5
6
7
Higher than 7
Off
On
Flash
4.8. Back up Settings and Calibration Data
The parameter settings and the calibration coefficients can be saved to a backup file after reading these data
from the FAD-40 instrument. This backup file can be re-written to FAD-40 after opening it by xFace.
The backup feature gives a service advantage to FAD-40 instruments. We propose to burn these files to CD /
DVD and save this backup CD / DVD in the control cabinet additionally to a backup file on your PC.
Important note:
The previous parameter settings and calibration coefficients in FAD-40 will get lost after
loading a backup to the instrument.