5.5.5 Label from the terminal board cover (inside)
31 32 33 34 35 36 37
1
3
6
7
8
9 10 11
+24V
counter
signal
-
analog IN
sensor
SPC m1/V1.0
45 46
48 49
51 52
N
16 17
22 23
25 26
N L
~
N L
signal in
mains supply
230V 50/60Hz
44
47
50
PE
15
21
24
PE
PE
extr
a - lo
w v
olta
ge
Terminal
42 43
N L
41
PE
19 20
18
12 13 14
38 39 40
fault
NC
NO
2
4
5
27 28 29 30
+24V /
Read the manual !
Bedienanweisung lesen !
+24V /
signal
-
GND
INPUT
FC OUT
OUT +
OUT
-
4 - 20 mA
refill IN 230V
FU/ FC
level
switch
pressure
switch
refill
release
FC
5A
5A
30
250
VDC
VAC
ohmic load
Stör
ung
FU
Standby
GND
sensor
sensor
ATTENTION:
Even if unit is isolated from
power supply, terminals 12,
13, 14, 16 and 17 may carry
230V voltage!
ACHTUNG:
Trotz Netztrennung kann, an
den Klemmen: 12, 13, 14, 16
und 17 eine Spannung von
230V anliegen !
FC
M
fault FC
system
temperature
pwm
pressure
vessel
pressure
analog
out
0 - 10 V
OUT
analog
out
motor ball valve
high v
olta
ge
(230V 50/60Hz)
option
L
RS232
option
11.06.2015
option
option
GND
GND
GND
GND
GND
A
A
GND
Klemmenplan Vacumat ECO 20150708
Explanation of the abbreviations on the label on the terminal board cover.
Note: The switch settings shown represent the current-free, non-switched state.
FU/FC
Frequency converter
refill IN 230V
Top-up signal input 230V
extra-low voltage
Protective low voltage
fault
Fault, common fault output
M
Motor (pump motor)
high voltage
Voltage as per markings
L
Phase
N
Neutral wire
PE
Protective earth (PE) conductor
mains supply
Power feed
NO
normally open (volt-free in open position)
NC
normally closed (volt-free in closed position)
pwm
Input for water meter with pulse output (option)
sensor
Sensor
system pressure
System pressure sensor input
vessel pressure
Vessel pressure sensor input
temperature
Temperature sensor input
FC out
FC out
ohmic load
Ohmic load, resistance
motor ball valve
Motor ball valve
level switch
Level switch / float switch / dry run protection
pressure switch
Pressure switch controlled degassing
refill
Top-up
release FC
release FC
standby
standby
mains supply
Mains feed
GND/AGND/GNDA
Mass (A=analogue, only connected as per terminal diagram)
out analogue
out analogue
Summary of Contents for Vacumat Eco 300
Page 4: ...4 ...
Page 28: ...28 ...
Page 52: ...52 ...
Page 76: ...76 ...
Page 100: ...100 ...
Page 124: ...124 ...
Page 148: ...148 ...
Page 172: ...172 ...
Page 196: ...196 ...
Page 220: ...220 ...
Page 244: ...244 ...
Page 268: ...268 ...
Page 292: ...292 ...
Page 316: ...316 ...
Page 340: ...340 ...
Page 364: ...364 ...