Installation Instructions
Seite/Page 76 - Kaptitel/Chapter 5: Installation Instructions
10.6.16
5.15.3 Electronic voltage control xControl
The xControl controls the generator voltageand motor speed. An actuator/servo on the injection pump can
increasethe engine speed compared to the idle speed.
If the generator runs without load, the frequency should be approx. 48,5 - 49 Hz (50 Hz System) or 58,5 - 59 Hz (60
Hz System). The frequency (equates to the speed) can be increased by up to 8%. This ensures that the engine
speed is increased when there is an extra load. The maximum speed is achieved when 80% load is reached.
The speed gauge is governed and limited by an adjusting screw, above and below. Adjustment of this screw may not
occur without the expressive approval of the manufacturer.
All signals pass through the circuit board in the xControl box. The signal impulse for the Servo is passed to the
electric motor.
5.15.4 Connection to the AC on-board power supply
5.15.4.1 Protective conductor
The generator is equipped with a PEN protective conductor system as standard. A Neutral and a PE line are
seperate on the power out cable.
If a separate protective conductor is necessary (i. e. according to national safety regulations), the bridge circuit at the
generator and the AC-Control box between neutral and generator housing has to be removed. Afterwards a
separate protective conductor has to be installed and connected to all the system’s attached metallic housings.
It is recommended to provide a voltage indication (voltmeter) and also a power indication, if applicable, in the
installation system. The voltmeter (and power indication, if applicable) has to be installed behind the selector switch
so that the voltage for every possible voltage source may be indicated. A separate voltmeter for the generator itself,
is therefore not required.
5.15.4.2 Electrical fuse
It is absolutely essential that the electrical system installation is inspected by a qualified electrical technician. The
generator should have its own AC input electrical fuse. This fuse should be sized so that the rated current of the
generator on each of the individual phases is not exceeded by more than 25%.
Data for gensets with power output greater than 30 kW on request!
The fuses must be of the slow type. A 3-way motor protection switch must be installed to protect the electrical motor.
Required fuse see
section 9.6, “Rated current,” on page 141.
5.15.4.3 Required cable crosssections
The following recommended electrical cable dimensions (cross sections) are the minimum required sizes for a safe
installation (see section 9.7, “Cable cross-section,” on page 141).
5.16 Generator DC system installation
The Panda generators from 6000 upwards have their own dynamo to charge a DC starter battery.
It is recommended to install an additional starter battery for the generator.
The generator is then independent from the remaining battery set. This enables you to start the genset at any time
with its own starter battery even if the other batteries are discharged. A further advantage of a separate starter
battery is that it isolates the generator's electric system from the rest of the boat's DC system, i.e. minus pole (-) is
not connected electrically to Earth/Ground.
The generator is then Earth/Ground free.
Summary of Contents for 10000x
Page 10: ...Seite Page 10 Kapitel Chapter 2 10 6 16 Leere Seite Intentionally blank...
Page 96: ...Installation Instructions Seite Page 96 Kaptitel Chapter 5 Installation Instructions 10 6 16...
Page 148: ...Seite Page 148 Kapitel Chapter 9 Appendix 10 6 16 Leere Seite Intentionally blank Appendix...
Page 149: ...Panda_xControl_eng R01 5 10 6 16 Panda xControl Manual...
Page 189: ...Panda xControl 10 6 16 Kapitel Chapter 11 Panda xControl Seite Page 189...