Installation Instructions
10.6.16
Kapitel/Chapter 5: Installation Instructions - Seite/Page 55
5.7
Ventilating the Fuel System
Normally, the fuel system is designed to ventilate air itself i.e. as soon as the electric starter motor starts operation
the fuel pump starts working and the fuel system will be de-aerated after some time automatically. It is nevertheless
essential to ventilate the system as follows prior to the first operation (as all hoses are empty):
1. Press switch „ON“. All functional elements must light up.
2. Press failure bypass switch and keep firmly pressed. The electrical fuel pump must be audible. Switching on and
off the solenoid valve at the generator will be audible by pressing the failure bypass switch (if capsule
removed).Pressing the failure bypass switch for approx 3 - 4 minutes will loosen the ventilation screw located at
the fuel solenoid valve. The button must continue to be pressed, whilst opening the screw. A large cloth or
Kleenex tissue must be laid beneath the connection to prevent escaping fuel running into the capsule. If the fuel
runs out without air bubbles, then the ventilation screw can be closed. Only then may the button be released.
3. Pressing the starter button can now start the machine. The machine should start after a short period. If this does
not occur, then a connecting nut fitted to the injection line must be loosened and starting procedure repeated.
Retighten the washers after successfully starting!
Fig. 5.7.0-1: Ventilation screw at the fuel solenoid valve
Ventilation screw at the fuel solenoid valve
Not all generator models are equipped with a fuel solenoid valve. At genera-
tors without a fuel solenoid valve, a single ventilation screw is installed.
Sample picture
5.8
Installation of the cooling system
5.8.1 The cooling system / general instructions
The Fischer Panda vehicle generator is delivered without a radiator, with the exception of generators with perma-
nently installed radiators such as the PVK-UK or the PSC series.
Depending on the purpose and installation situation, a wide variety of Fischer Panda radiators are available for the
optimum customization of the system. Operation with a commercially available vehicle radiator is possible. The cor-
responding dimensioning must be implemented by the installer.
Note:
For generators with a permanently installed radiator (e.g.
PVK-UK series), the radiator dimensioning and the
installation are not necessary.
5.9
Radiator baseplate
The radiator baseplate shall be dimensioned in accordance with the purpose. The corresponding checks and entries
in the vehicle papers shall be implemented by the operator.
Summary of Contents for 10000x
Page 10: ...Seite Page 10 Kapitel Chapter 2 10 6 16 Leere Seite Intentionally blank...
Page 96: ...Installation Instructions Seite Page 96 Kaptitel Chapter 5 Installation Instructions 10 6 16...
Page 148: ...Seite Page 148 Kapitel Chapter 9 Appendix 10 6 16 Leere Seite Intentionally blank Appendix...
Page 149: ...Panda_xControl_eng R01 5 10 6 16 Panda xControl Manual...
Page 189: ...Panda xControl 10 6 16 Kapitel Chapter 11 Panda xControl Seite Page 189...