25
of
27
4.
Specifications and Approvals.
4.1
NXO2TRIM Oxygen Probe Interface
Supply voltage (CANbus)
Power consumption
Supply frequency
Ambient temperature range
Protection category
Unit dimensions
Weight
Interface to NX6100 or PPC-6000 series.
Interface to oxygen probe.
Oxygen sensor heater supply.
Oxygen sensor temperature set point.
Oxygen measurement accuracy
Auxiliary Inputs:
Type
Input impedance
Pre-assignment
Flue gas temperature input:
Type
Measurement range
Flue temperature accuracy
26 Vac
15%
Approximately 10 VA
50/60 Hz
5%
0 to 60 °C
IP65.
160 x 110 x 75 mm deep
(6.29 x 4.3 x 2.9 in deep)
0.6 kg
Fireye specific CANbus.
Fireye specific.
24 Vac nominal
820 °C (1,508 °F)
±1% of value.
4– 20mA.
220
O2, CO
Type-K thermocouple.
0-540 °C (1000 °F)
± 2 °C (35.6 °F)