27

4.

The unit moves the air drives up to the point above the current set point, leaving the fuel drive
in the same position.

The display will show ‘Flow calc An + 1’

.

5.

When the new oxygen reading settles, the unit calculates and stores the new flow value. If
the oxygen reading exceeds 15.0% during this stage, the unit shuts the burner down with
F77.

6.

When the unit has completed the low fire point, the measured boiler transport delay (at low
fire) is stored in option parameter 30.7.  Option parameter 30.5 (oxygen trim enable) is set to
zero.

7.

You must use “adjust ratio” mode to confirm each position from P3 (low fire) to Ph (high fire).
If the flow values appear reasonable (about 4 to 6% change at each position) once you have
finished, setting option 30.5 to 1 will enable O2 trim. There is a one-minute delay after exiting
commissioning mode before trim will enable. If the flow values are unreasonable, they may
be adjusted manually by placing the cursor to the “FLO” position and using the up/down
arrows set the desired flow value. Using EK44 verify the O2 levels at each position and adjust
to match if required. EK46 will help troubleshoot O2 trim issues.

BEFORE ENABLING TRIM, USE ADJUSTS RATIO MODE TO MANUALLY CHECK THE
CALCULATED FLOW VALUES, OXYGEN SETPOINTS AND TRANSPORT DELAY.  THE LOW FIRE
PERCENTAGE FLOW VALUE SHOULD CONFORM APPROXIMATELY TO THE TURN-DOWN RATIO
OF THE BURNER.

SUMMARY

To perform automatic trim commissioning, follow the procedure below:

1.

If the probe is new, enter the offset and gain values in option parameters 30.1 and 30.2 which
are supplied with the probe. To re-calibrate the probe referto section 8.

2.

Enter adjust ratio mode (See section 5).

3.

Enable automatic trim commissioning by setting option parameter 30.9 to 1.

4.

Wait for procedure to finish.

5.

Check that the 0

2

, flow and transport delay values are sensible. Use EK44 for O2 value.

6.

Check calibration of the oxygen probe.

7.

Confirm setup using “adjust ratio” mode.

NOTE:

If the boiler shuts off for any reason during automatic commissioning, the sequence will continue
when the boiler re-starts.

Option parameter

30.9 value

Meaning

0

Not selected.

1

Perform automatic trim characterization.

The control will attempt to

characterize the burner profile by calculating flow values and selecting oxygen
set points to match the currently commissioned points.

Automatic trim commissioning will be performed under the following
conditions:

An oxygen probe is fitted and fully operational

The control is in adjust ratio mode.

A hydrocarbon ratio has been entered for the current fuel (see option
parameters 35.1 – 35.4).

Summary of Contents for NEXUS NX6100 series

Page 1: ...1 of 27 Type2 Oxygen probe system for Nexus NX6100 and PPC6000 Supplement to NEX6101 PPC6001 NXPK2244 July 24 2019...

Page 2: ...Connection of Line voltages to the NXO2TRIM will damage the product beyond repair The interconnection system between the NXO2TRIM and the NXPK224455 56 57probes is considerably different to the wiring...

Page 3: ...3 of 27...

Page 4: ...4 of 27...

Page 5: ...mum cable length limitations Cabinet designers MUST ensure that Line voltage and Extra Low Voltage ELV cables are segregated within the burner cabinet distribution panels and conduits The manufacturer...

Page 6: ...series controller must be to the CANbus 4 core screen cable specification in the main product manual NEX 6101 or PPC 6001 Connect the CAN cable braid screen at the controller using the screen terminat...

Page 7: ...4 20mA Input 3 0 5V PG9 O2 Trim Interface GND 4 20mA Input 0V 0V PH1 O2 Trim Interface Probe 1 Black 0 14V PH2 O2 Trim Interface Probe 2 Red 0 14V PH3 O2 Trim Interface Probe 3 Yellow 0 14V PH4 O2 Tri...

Page 8: ...es on this face Probe connection terminals PH1 to PH8 CAN and 4 20mA connection terminals PG1 to PG8 Ring terminal point for screen termination Internal view of NXO2TRIM Do not Connect 120Vac NXO2TRIM...

Page 9: ...27 Calibration port Removable terminal block NOTE There is no screen termination point The screen in the 6 way cable must be cut short to the PVC outer cover View of NXPK224455 56 57 oxygen probe term...

Page 10: ...SAFE AFTER COMPLETION Additionally the oxygen probe calibration should be checked before and after the procedure since the results depend highly upon measurements taken using the probe Before proceed...

Page 11: ...hown on the display use the scroll keys to position the pointing to the O2 value use the UP DOWN keys to adjust the oxygen setpoint as necessary The display will start flashing to indicate that a chan...

Page 12: ...ption 30 1 Oxygen probe calibration offset value 0 999 LV3 This option parameter is only available if option 30 0 is non zero This option parameter must be set to the calibration offset value that is...

Page 13: ...below Option parameter 30 5 value Meaning 0 Monitor only The oxygen value is only used to provide a display of the measured oxygen level 1 Closed loop trim The oxygen value is used to provide both a d...

Page 14: ...e burner modulates Only the trim profile is affected The Oxygen set points and flow values are not changed This option parameter allows the learned trim profile to be reset If the option is set to 1 a...

Page 15: ...MODE TO MANUALLY CHECK THE CALCULATED FLOW VALUES OXYGEN SETPOINTS AND TRANSPORT DELAY THE LOW FIRE PERCENTAGE FLOW VALUE SHOULD CONFORM APPROXIMATELY TO THE TURN DOWN RATIO OF THE BURNER SUMMARY To p...

Page 16: ...the trimmed drives will still be attained Option parameter 31 0 value Meaning 0 Modulation not limited Burner modulates from P3 to Ph Oxygen trim works over full range from P3 to Ph but may not be ab...

Page 17: ...instead of 25 Options 33 1 to 33 4 Trim integral gain Default 10 LV3 Options 33 1 to 33 4 are only available if option 30 5 oxygen input function has been set for closed loop oxygen trim In order for...

Page 18: ...ess enter 7 Wait until the oxygen reading has stabilized then record the excess air value at location b1 in the table relating to the current profile position 8 Repeat the above for all other profile...

Page 19: ...b3 c3 d3 e3 c3 d3 f3 e3 f2 g3 f3 y c3 4 A a4 b4 c4 d4 e4 c4 d4 f4 e4 f3 g4 f4 y c4 5 A a5 b5 c5 d5 e5 c5 d5 f5 e5 f4 g5 f5 y c5 6 A a6 b6 c6 d6 e6 c6 d6 f6 e6 f5 g6 f6 y c6 7 A a7 b7 c7 d7 e7 c7 d7 f7...

Page 20: ...an upward direction will scroll through all temperature sensor options available until 0 nothing is displayed Enter this value to disconnect the specified device from any hardware Scrolling the list i...

Page 21: ...fuels These values should be used as a guide only If the display is required to show gross efficiency in addition to entering the gross calorific values a non zero value for the boiler radiated heat l...

Page 22: ...to the option parameter that relates to the selected profile If the burner is not firing the high alarm value for any profile selection may be adjusted When the flue temperature rises above the high a...

Page 23: ...value entered relates to a percentage deviation from each oxygen set point in the firing range If the burner is firing it is only possible to make an adjustment to the option parameters that relate to...

Page 24: ...ault codes There is one change that will be observed in the EK data The EK72 value Oxygen Probe Cell Temperature will be higher for the NXPK224455 56 57 oxygen probe The normal value will be 820 C 1 5...

Page 25: ...gen sensor heater supply Oxygen sensor temperature set point Oxygen measurement accuracy Auxiliary Inputs Type Input impedance Pre assignment Flue gas temperature input Type Measurement range Flue tem...

Page 26: ...r replacement pressure Unit Weight 0 to 70 C 0 to 158 F IP20 600 C 1 112 F Zirconia oxide cell 1 21 Oxygen 5s Less than 15s for 63 change Type K thermocouple Ambient air at 20 9 O2 3 O2 in Nitrogen 35...

Page 27: ...ich is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES...

Reviews: