4.2
NX6083-x Flue Gas Temperature and Oxygen probe
Ambient temperature range
Protection category
Maximum flue temperature
Oxygen Measurement:
Type
Range
Response.
Time constant.
Flue Gas Temperature Measurement
Calibration:
Reference gas concentration
Recommended calibration gas
concentration
Reference and Calibration gas flow rate
Filter and flame arrestor
Filter pressure drop
Filter replacement pressure
Unit Weight
0 to 70 °C (0 to 158 °F)
IP20.
600 °C ( 1,112 °F)
Zirconia oxide cell,
1 – 21% Oxygen.
5s
Less than 15s for 63% change.
Type K thermocouple
Ambient air at 20.9% O
2
3% O
2
in Nitrogen
350 cc/min
4 – 7 micron sintered stainless steel.
50 – 100 mm water gauge.
150 mm water gauge.
2.5 – 4.5 kg (type dependent)
5.5 – 9.9 lb (type dependant)
4.3
Approvals
Europe: Tested in accordance with the Gas Appliances Regulation (EU) 2018/426 (GAR) including
the following standards:
EN298-2012, EN12067-2
Australia: Approved for use by AGA.
Relevant Standards: EN298-2012, AS4625, AS 4630.
North America:
UL approved.