Using adjust ratio mode to modify and existing oxygen profile manually, follow steps 1 -12
listed below.

To adjust an oxygen set point or enter an air flow value in the firing range, use the following procedure.
The manual calculation of the values to be entered here is covered in the next section.

1.

Enter adjust ratio mode (See section 5.6).

2.

Ensure oxygen trim is set to monitor only 30.5 = 0.

3.

Use the scroll keys to select the desired set point and move up and/or down (A4 for
example). The system will modulate to the selected set point and the number displayed will
flash to indicate that the drives are modulating.

4.

Wait for the number in the display to be illuminated steadily. This means that the drives have
arrived at the selected set point.

5.

The display will allow scrolling sideways to show flow and ‘O2’ in addition to the servo-motor
positions to indicate that the system is expecting a flow value and an oxygen set point to be
entered for the current profile set point.

To check the current oxygen measured value use

the engineer’s key EK44.

6.

Once the oxygen value is shown on the display use the scroll keys to position the ‘>’ pointing
to the ‘O2’ value use the UP/DOWN keys to adjust the oxygen setpoint as necessary. The
display will start flashing to indicate that a change has been made.

7.

If the new oxygen set point value is wanted, press the ENTER key. The value will be stored in
memory.

8.

If the new oxygen set point value is not wanted or an adjustment is not required, press the

NEXT

key to return to the value stored in memory.

9.

Once the flow value is shown on the display use the scroll keys to position the’>’ pointing to
the ‘FLO’ value use the UP/DOWN keys to adjust the flow value as necessary. The display
will show the air flow value, represented as a percentage of the air flow when the drives are
at the

HIGH FIRE

position. The display will start flashing to indicate that a change has been

made.

10.

If the new flow value is not wanted or an adjustment is not required, press the

NEXT

key to

return to the value stored in memory.

11.

If it is necessary to adjust another set point in the firing range, repeat the above procedure
from step 3.

CAUTION

When using the adjust ratio mode, it is not possible for the unit to check drive

positions at all times.  It is the responsibility of the engineer to check that motors

and valves are responding correctly.

Summary of Contents for NEXUS NX6100 series

Page 1: ...1 of 27 Type2 Oxygen probe system for Nexus NX6100 and PPC6000 Supplement to NEX6101 PPC6001 NXPK2244 July 24 2019...

Page 2: ...Connection of Line voltages to the NXO2TRIM will damage the product beyond repair The interconnection system between the NXO2TRIM and the NXPK224455 56 57probes is considerably different to the wiring...

Page 3: ...3 of 27...

Page 4: ...4 of 27...

Page 5: ...mum cable length limitations Cabinet designers MUST ensure that Line voltage and Extra Low Voltage ELV cables are segregated within the burner cabinet distribution panels and conduits The manufacturer...

Page 6: ...series controller must be to the CANbus 4 core screen cable specification in the main product manual NEX 6101 or PPC 6001 Connect the CAN cable braid screen at the controller using the screen terminat...

Page 7: ...4 20mA Input 3 0 5V PG9 O2 Trim Interface GND 4 20mA Input 0V 0V PH1 O2 Trim Interface Probe 1 Black 0 14V PH2 O2 Trim Interface Probe 2 Red 0 14V PH3 O2 Trim Interface Probe 3 Yellow 0 14V PH4 O2 Tri...

Page 8: ...es on this face Probe connection terminals PH1 to PH8 CAN and 4 20mA connection terminals PG1 to PG8 Ring terminal point for screen termination Internal view of NXO2TRIM Do not Connect 120Vac NXO2TRIM...

Page 9: ...27 Calibration port Removable terminal block NOTE There is no screen termination point The screen in the 6 way cable must be cut short to the PVC outer cover View of NXPK224455 56 57 oxygen probe term...

Page 10: ...SAFE AFTER COMPLETION Additionally the oxygen probe calibration should be checked before and after the procedure since the results depend highly upon measurements taken using the probe Before proceed...

Page 11: ...hown on the display use the scroll keys to position the pointing to the O2 value use the UP DOWN keys to adjust the oxygen setpoint as necessary The display will start flashing to indicate that a chan...

Page 12: ...ption 30 1 Oxygen probe calibration offset value 0 999 LV3 This option parameter is only available if option 30 0 is non zero This option parameter must be set to the calibration offset value that is...

Page 13: ...below Option parameter 30 5 value Meaning 0 Monitor only The oxygen value is only used to provide a display of the measured oxygen level 1 Closed loop trim The oxygen value is used to provide both a d...

Page 14: ...e burner modulates Only the trim profile is affected The Oxygen set points and flow values are not changed This option parameter allows the learned trim profile to be reset If the option is set to 1 a...

Page 15: ...MODE TO MANUALLY CHECK THE CALCULATED FLOW VALUES OXYGEN SETPOINTS AND TRANSPORT DELAY THE LOW FIRE PERCENTAGE FLOW VALUE SHOULD CONFORM APPROXIMATELY TO THE TURN DOWN RATIO OF THE BURNER SUMMARY To p...

Page 16: ...the trimmed drives will still be attained Option parameter 31 0 value Meaning 0 Modulation not limited Burner modulates from P3 to Ph Oxygen trim works over full range from P3 to Ph but may not be ab...

Page 17: ...instead of 25 Options 33 1 to 33 4 Trim integral gain Default 10 LV3 Options 33 1 to 33 4 are only available if option 30 5 oxygen input function has been set for closed loop oxygen trim In order for...

Page 18: ...ess enter 7 Wait until the oxygen reading has stabilized then record the excess air value at location b1 in the table relating to the current profile position 8 Repeat the above for all other profile...

Page 19: ...b3 c3 d3 e3 c3 d3 f3 e3 f2 g3 f3 y c3 4 A a4 b4 c4 d4 e4 c4 d4 f4 e4 f3 g4 f4 y c4 5 A a5 b5 c5 d5 e5 c5 d5 f5 e5 f4 g5 f5 y c5 6 A a6 b6 c6 d6 e6 c6 d6 f6 e6 f5 g6 f6 y c6 7 A a7 b7 c7 d7 e7 c7 d7 f7...

Page 20: ...an upward direction will scroll through all temperature sensor options available until 0 nothing is displayed Enter this value to disconnect the specified device from any hardware Scrolling the list i...

Page 21: ...fuels These values should be used as a guide only If the display is required to show gross efficiency in addition to entering the gross calorific values a non zero value for the boiler radiated heat l...

Page 22: ...to the option parameter that relates to the selected profile If the burner is not firing the high alarm value for any profile selection may be adjusted When the flue temperature rises above the high a...

Page 23: ...value entered relates to a percentage deviation from each oxygen set point in the firing range If the burner is firing it is only possible to make an adjustment to the option parameters that relate to...

Page 24: ...ault codes There is one change that will be observed in the EK data The EK72 value Oxygen Probe Cell Temperature will be higher for the NXPK224455 56 57 oxygen probe The normal value will be 820 C 1 5...

Page 25: ...gen sensor heater supply Oxygen sensor temperature set point Oxygen measurement accuracy Auxiliary Inputs Type Input impedance Pre assignment Flue gas temperature input Type Measurement range Flue tem...

Page 26: ...r replacement pressure Unit Weight 0 to 70 C 0 to 158 F IP20 600 C 1 112 F Zirconia oxide cell 1 21 Oxygen 5s Less than 15s for 63 change Type K thermocouple Ambient air at 20 9 O2 3 O2 in Nitrogen 35...

Page 27: ...ich is found defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES...

Reviews: