![Festo s CMMD-AS-C8-3A Mounting And Installation Download Page 63](http://html1.mh-extra.com/html/festo/s-cmmd-as-c8-3a/s-cmmd-as-c8-3a_mounting-and-installation_2283257063.webp)
B
Diagnostic messages
Festo – GDCP-CMMD-AS-HW-EN – 1404NH – English
63
Error group 22
PROFIBUS
no.
Reaction
Message
Code
22-2
7500h
PROFIBUS communication error
configurable
Cause
–
Faulty initialisation of the Profibus interface.
–
Interface defective.
Action
•
Check the set slave address.
•
Check bus termination.
•
Check wiring.
Error group 25
Firmware
no.
Code
Message
Reaction
25-1
6081 h
Incorrect firmware
PS off
Cause
Motor controller and firmware are not compatible.
Action
•
Update the firmware.
Error group 26
Data flash
no.
Code
Message
Reaction
26-1
5581h
Checksum error
PS off
Cause
Checksum error of a parameter set.
Action
•
Load factory setting.
•
If the error is still present, the hardware is defective.
Error group 29
SD card
no.
Code
Message
Reaction
29-0
7680h
No SD available
configurable
Cause
An attempt was made to access a missing SD card.
Action
Check:
•
whether the SD card is inserted properly,
•
whether the SD card is formatted,
•
whether a compatible SD card is plugged in.
29-1
7681h
SD initialization error
configurable
Cause
–
Error during initialization.
–
Communication not possible.
Action
•
Plug card back in.
•
Check card (file format FAT 16).
•
If necessary, format card.