3. Input module CPX-P-8DE-N-...
3-38
Festo P.BE-CPX-P-EA-EN en 1209NH English
Module parameter: Counter configuration channel 0 … 3
Handheld
This parameter is only available in the extended process image (miniature switch = ON).
Function no.
4828 + m * 64 +
16
m = Module number (0 ... 47)
Description
Only effective in operating mode B (counter): Specifies the counting direction
and edge polarity for the respective input channel (only channel 0 ... 3).
An alteration of the parameter causes an initialisation of the respective channel.
Bit
Counter configuration
Bit 0: Edge polarity channel 0
Bit 1: Edge polarity channel 1
Bit 2: Edge polarity channel 2
Bit 3: Edge polarity channel 3
Bit 4: Counting direction channel 0
Bit 5: Counting direction channel 1
Bit 6: Counting direction channel 2
Bit 7: Counting direction channel 3
[Counter control]
[Ch 0 edge]
[Ch 1 edge]
[Ch 2 edge]
[Ch 3 edge]
[Ch 0 direction]
[Ch 1 direction]
[Ch 2 direction]
[Ch 3 direction]
Values
Edge polarity (Bit 0 … 3)
0
1
positive edge (presetting)
negative edge
[rising]
[falling]
Counting direction (bit 4 … 7)
0
1
count upwards (presetting)
count downwards
[up]
[down]
Comment
If the counter configuration is changed, the counter is initialised!
If the debounce time is active, counting is effected to the edge of the debounced
signal.
Tab. 3/30:
Counter configuration (channel-specific, channel 0 … 3)
Summary of Contents for CPX-P-8DE-N Series
Page 2: ......
Page 34: ...1 Overview and connection technology 1 14 Festo P BE CPX P EA EN en 1209NH English...
Page 50: ...2 Mounting and dismantling 2 16 Festo P BE CPX P EA EN en 1209NH English...
Page 113: ...Technical appendix A 1 Festo P BE CPX P EA EN en 1209NH English Appendix A Technical appendix...
Page 125: ...Index B 1 Festo P BE CPX P EA EN en 1209NH English Appendix B Index...
Page 126: ...B Index B 2 Festo P BE CPX P EA EN en 1209NH English Table of contents B Index B 1...
Page 132: ...B Index B 8 Festo P BE CPX P EA EN en 1209NH English...