3. Input module CPX-P-8DE-N-...
3-36
Festo P.BE-CPX-P-EA-EN en 1209NH English
Detailed information regarding the input debounce time can
be found in the CPX system description. The parameter,
however, is module-specific for many other input modules
and influences the behaviour of the entire module. In the
CPX-P-8DE-N-... it is a channel-specific parameter that spe-
cifies the behaviour of an individual channel.
Module parameter: Input debounce time channel 4 … 7
Handheld
Function no.
4828 + m * 64 +
13
m = Module number (0 ... 47)
Description
Tab. 3/26
Bit
Input debounce time channel 4 … 7
[Input debounce time]
Bit:
1,
3,
5,
7,
0
2
4
6
Duct 4
Duct 5
Duct 6
Duct 7
[Ch 4]
[Ch 5]
[Ch 6]
[Ch 7]
Values
0
0
1
1
0
1
0
1
Disabled
3 ms (presetting)
10 ms
20 ms
[Inactive]
[3 ms]
[10 ms]
[20 ms]
Comment
Tab. 3/26
Tab. 3/27:
Input debounce time channel 4 … 7 (channel-specific)