1. Installation
1-24
Festo P.BE-CPV-CO3-EN en 1201a
1.4
Bus termination with terminating resistors
Note
Always
use a bus termination at both ends of the field bus.
This also applies if the CPV Direct is at the end of the field
bus.
If you use T-adapters, install the terminating resistor at the
unused output of the T-adapter.
Recommendation:
Fit a resistor (120 Ω, 0.25 W, see following fig.) for the bus
termination in the Festo field bus plug.
1
Protective cap
2
Resistor for bus
connection
(120 Ω, 0.25 W)
V+
GN
D H L
SL
D
V+
GN
D H L
SL
D
V+
GND
H L
SL
D
1
2
Fig. 1/7:
Bus termination with resistor in the field bus plug from Festo
1.4.1
Install a terminating resistor using the adapters
If the CPV valve terminal to be connected is at the end of the
field bus, a terminating resistor (120 Ω, 0.25 W) must be
fitted in the field bus socket.
•
Connect the terminating resistor between the cores for
CAN_H and CAN_L.
Summary of Contents for CPV...-GE-CO3-8 series
Page 2: ......
Page 14: ...Contents and general instructions XII Festo P BE CPV CO3 EN en 1201a...
Page 15: ...Installation 1 1 Festo P BE CPV CO3 EN en 1201a Chapter 1 Installation...
Page 59: ...Commissioning 2 1 Festo P BE CPV CO3 EN en 1201a Chapter 2 Commissioning...
Page 78: ...2 Commissioning 2 20 Festo P BE CPV CO3 EN en 1201a...
Page 98: ...3 Diagnosis and error treatment 3 20 Festo P BE CPV CO3 EN en 1201a...
Page 105: ...Object directories B 1 Festo P BE CPV CO3 EN en 1201a Appendix B Object directories...
Page 129: ...Examples C 1 Festo P BE CPV CO3 EN en 1201a Appendix C Examples...
Page 136: ...C Examples C 8 Festo P BE CPV CO3 EN en 1201a...
Page 137: ...Index D 1 Festo P BE CPV CO3 EN en 1201a Appendix D Index...
Page 138: ...D Index D 2 Festo P BE CPV CO3 EN en 1201a Contents D Index D 1...