System manual CECX / Connections and wiring
13.3 General limits for wire cross sections
13.3.1 Minimum cross section according to norm
The minimum cross sections in mechanical engineering are defined in
EN60204 "Electrical and electronic equipment and systems" in chapter
"Conductors, cables, wires" and in chapter 14 "Wiring technology", particu-
larly under "Wiring outside of housings".
Extract from EN60204-1:1997:
"...
13.6 Minimum cross section
To guarantee sufficient mechanical strength, the conductor cross section
should not be smaller than that given in table 6. Wherever it is regarded as
necessary, conductors with smaller cross sections as given in table 6 may
be used in the equipment, under the condition that, sufficient mechanical
strength is achieved in another way and trouble free function is not im-
paired.
Table 6: Minimum cross sections for copper conductors
Description of conductors, cables and lines
Order Application
One core,
multi-core
One core,
solid
Two-core,
shielded
Two-core,
unshielded
Three or more
core, shielded
or not
Outside the
housing
Not flexible,
Main circuit
Connection to ma-
chine parts that are
subject to frequent
movement
Connection in con-
trol circuit
Wiring in data
transmission system
1
1
1
-
1.5
-
1.5
-
0.75
1
0.3
-
0.75
1
0.5
-
0.75
1
0.3
0.08
Inside the
housing
Not flexible,
Main circuit
Connection in con-
trol circuit
Wiring in data
transmission system
0.75
0.2
-
0.75
0.2
-
0.75
0.2
-
0.75
0.2
-
0.75
0.2
0.08
NOTE: all cross sections are listed in mm².
..."
For the minimum cross sections in plant construction, the constructions of
EN50178: "Equipping power plants with electronic apparatus" must be ob-
served.
Further instructions for wiring are stated in EN61131 "Programmable con-
trollers" Part 4 "User guidelines".
CECX-II 13-11
Summary of Contents for CECX-X-C1 Series
Page 1: ...Manual Controller Modular CECX CECX X C1 CECX X M1 761886 1112c en ...
Page 2: ...1112c en ...
Page 4: ......
Page 6: ...1112c en ...
Page 7: ...CECX modular control system CECX modular control system ...
Page 46: ...CECX modular control system CECX I 38 ...
Page 47: ...System manual CECX ...
Page 48: ...CECX II ...
Page 56: ...Content System Manual CECX VIII ...
Page 58: ...System manual CECX Product design CECX II 0 2 ...
Page 68: ...System manual CECX Safety notes CECX II 2 6 ...
Page 76: ...System manual CECX System overview CECX II 3 8 ...
Page 84: ...System manual CECX General assembly and installation instructions CECX II 4 8 ...
Page 118: ...System manual CECX Operating behavior CECX II 8 6 ...
Page 122: ...System manual CECX Disposal CECX II 10 2 ...
Page 124: ...System manual CECX Technical data CECX II 11 2 ...
Page 166: ......
Page 180: ......
Page 212: ......
Page 232: ......
Page 248: ......
Page 260: ......
Page 278: ......
Page 294: ......
Page 308: ......
Page 412: ......
Page 426: ......
Page 500: ...System manual CECX Bus link module CECX B CO CECX II 34 64 ...
Page 501: ...The library Ethernet lib The library Ethernet lib ...
Page 505: ...The library EventData lib The library EventData lib ...
Page 511: ...The library IncEnc lib The library IncEnc lib ...
Page 517: ...The Festo_EasyIP lib library ...
Page 532: ......
Page 535: ...The library PLCService lib The library PLCService lib ...
Page 542: ...The library PLCService lib CECX VII 6 ...
Page 543: ...The library SysLibComEx lib The library SysLibComEx lib ...
Page 547: ...The Festo_Motion lib library ...
Page 584: ......
Page 585: ...The Festo_PartDetector lib library ...
Page 601: ...FED VipWin interface ...
Page 630: ......