ALARMS
Fault code
Fault
Possible cause
Cure
F56 - A56
Calibration fault
Incorrect parameters
Check parameters and carry out a 100% calibration
Electrode damaged or not correctly positioned. Check the position of the electrode, replace it if necessary. After
replacement, repeat the 100% calibration
Recirculation of fumes inside the boiler
Check the tightness of the flue pipe and the seal of gaskets
Calibration procedure
not completed
Poor primary circuit circulation or poor dissipa-
tion during calibration
Reset the fault. Turn on the hot water faucet and wait for the
flame to stop flashing (about 2 minutes)
F61 - A61
Controller AGC01
fault
Controller AGC01 internal error
Check the ground connection.
Check the electrode.
Repeat the 100% calibration procedure.
If necessary replace the control unit.
A63
Controller AGC01
fault
Unstable power supply
Check the power supply
Controller AGC01 internal error
If necessary replace the control unit
A54 - A55
F62 - F63
Combustion fault
Insufficient system gas pressure
Check the gas supply pressure
Unstable grid voltage
Check the supply voltage
Electrode damaged or not correctly positioned
Check ignition electrode and ground
Turn off power supply for 10 seconds, reset the fault and perform
a 100% calibration (Sc15=1).
F67
BCC Service key connected
Load the parameters
F68 - A68
BCC Service key er-
ror
Error loading BCC Service key file
Repeat the loading procedure within 5 minutes from the boiler
power supply and replace the BCC Service key if necessary
A62
No communication
between controller
and gas valve
Controller not connected
Connect the controller to the valve
Valve damaged Replace valve
Check the wiring or replace the valve
A64
Maximum number of
consecutive Resets
exceeded
Maximum number of consecutive Resets excee-
ded
Disconnect the power supply to the boiler for 60 seconds and
then reinstate the boiler
F66
Firmware not loaded successfully
Reload the firmware or replace the card
Summary of Contents for OMNIA HYBRID C
Page 34: ...34 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU 7 2 Menu structure ...
Page 35: ...35 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU DHW mode is setting OFF ...
Page 36: ...36 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU ...
Page 51: ...51 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU ...
Page 53: ...53 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU U ...
Page 100: ...100 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Principle scheme ...
Page 101: ...101 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Electronic heat pump board ...
Page 102: ...102 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Wiring board ...
Page 113: ...113 EN Cod 3541T090 Rev 00 06 2019 ...
Page 114: ...114 EN Cod 3541T090 Rev 00 06 2019 ...