MANAGEMENT PARAMETERS HEAT PUMP AND BOILER IN HEATING MODE
13. MANAGEMENT PARAMETERS HEAT PUMP AND BOILER IN HEATING MODE
For heating mode it is possible to have two different heat pump and boiler activation logics depending on the parameters indicated in the following table and available
under the “8.2 REMOTE CONTROLLER - SERVICE menù” on page 50.
Parameter
DESCRIPTION Parameter
Factory setting
Reference paragraph
T4HMIN
Minimum external air temperature for heat pump heat mode
-5°C
“8.5 HEAT mode setting” on page 55
T4HMAX
Maximum outside air temperature for heat pump heat mode
25°C
“8.5 HEAT mode setting” on page 55
T4_AHS_ON
External air temperature for boiler activation
2°C
“8.10 AHS (bolier)” on page 57
t_ASH_DELAY
Boiler activation delay
30 min
“8.10 AHS (bolier)” on page 57
13.1 Boiler in integration to the heat pump (factory setting)
With external air temperature greater than (T4_AHS_ON - 2) the system heating is guaranteed by the heat pump only
See “fig. 171 - Heating with heat pump” on page 85
With external air temperature between (T4HMIN) and (T4_AHS_ON - 2) the system heating is guaranteed by the heat pump and the boiler: the boiler will be activated
if after the time (t_AHS_DELAY) the heat pump does not satisfy the setpoint.
See “fig. 173 - Heating with heat pump and boiler” on page 85
With external air temperature lower than T4HMIN the heating system is guaranteed only by the boiler.
Functional diagram with factory settings
-5
T4HMIN
-4
1
-20
OFF
ON
OFF
ON
BOILER
RISCALDAMENTO IMPIANTO
CALDAIA IN INTEGRAZIONE ALLA POMPA DI CALORE
Esempio con parametri T4HMIN= -5 e T4_AHS_ON= 2
0
T4_AHS_ON - 2
2
T4_AHS_ON
Texternal air
25
T4HMAX
It works only the boiler that will
be activated immediately
The boiler is activated in integration to the
heat pump after time t_AHS_DELAY (default 30 min)
It works only
the heat pump
HE
AT
PUMP
fig. 168 -
☞
NOTE:
To optimize the energy efficiency of the boiler it is suggested to set the boiler heating setpoint to the same value as the heat pump set point.
Summary of Contents for OMNIA HYBRID C
Page 34: ...34 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU 7 2 Menu structure ...
Page 35: ...35 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU DHW mode is setting OFF ...
Page 36: ...36 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER USER MENU ...
Page 51: ...51 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU ...
Page 53: ...53 EN Cod 3541T090 Rev 00 06 2019 REMOTE CONTROLLER SERVICE MENU U ...
Page 100: ...100 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Principle scheme ...
Page 101: ...101 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Electronic heat pump board ...
Page 102: ...102 EN Cod 3541T090 Rev 00 06 2019 ELECTRICAL DIAGRAM INDOOR UNIT Wiring board ...
Page 113: ...113 EN Cod 3541T090 Rev 00 06 2019 ...
Page 114: ...114 EN Cod 3541T090 Rev 00 06 2019 ...