Operating Instructions
VEK CN1-1
6 12/11
FEIG ELECTRONIC GmbH
1.5 Relay
Output
The relay output signals „Free Parking Area“ or “Used Parking Area”. The relay changeover contact can directly
control a traffic light. The method of operating for the relay can be set on load current principle or rest current
principle (see 2.4.5 Output settings). The LED displays the status of the relay.
Output Status
Relay Operating
Principle
Relay LED
Free
Load Current Principle
energized
Off
Used
Load Current Principle
de-energized
On
Free
Rest Current Principle
de-energized
On
Used
Rest Current Principle
energized
Off
If the operating of the output isn´t used, the output state can be manually set on „always free“ or „always used“
(see 2.3.3 Set Relay Output manually to “Free” or “Occupied”).
1.6 State Storage during Voltage Breakdown
During voltage breakdowns the setting values and the counter states remain unchanged. After the voltage returns
the counter works on normally. A flashing display shows the counter state must be checked and maybe fixed (see
2.3.1 Power Failure).