background image

mr

.

steam

®

C U S E R I E S

Installation, Operating & Maintenance Manual

INSTRUCTIONS FOR ELEMENT REPLACEMENT

READ INSTRUCTIONS COMPLETELY BEFORE STARTING WORK

Models

 

CU360

 

-

 

CU1400

 

use

 

probes

 

for

 

liquid

 

level

 

sensing

and

 

control.

 

Model

 

CU2000

 

and

 

higher

 

use

 

McDonnell-Miller

 

MM

 

150.

1.

Disconnect boiler from electric power supply at main safety switch or fuse panel.

Then turn boiler switch to “OFF" position.

2.

Close water supply valve on incoming water supply line.

Drain boiler completely of water.

3.

Open boiler door to access heating element.

4.

Disconnect wire (electric) leads connecting element to main power

system of boiler. Again, note wire connections to facilitate re-assembly.
Proceed to remove and discard (6) bolts from flange.

The wire connections to facilitate re-assembly (see wiring schematic).

Remove and discard six (5/16"-18) bolts from flange. Do not reuse these bolts.

5.

Thoroughly clean boiler flange of all foreign material. Be certain no part of old

gasket remains on flange.

6.

Proceed to install element flange assembly with gasket between boiler flange
and element flange. In doing this, be careful to align flange holes so element wire
connection terminals on element assembly are in line with previously disconnected
wire leads to facilitate easy connections.

Observe markings on element flange. Install element marking

“TOP” on top.

7.

Use only new element flange bolts. Tighten all (6) element flange bolts to a torque

value of 22 lb-ft each (see illustration).

8.

Connect all wires to the terminals. Tighten all element terminals to a torque value

of 20 lb-in each (see illustration). Make sure all wires are clean and bright to
assure good electrical contact.

9.

Check that the wires are correctly connected to the contactor terminals and are

tightened to a torque listed on the contactor (ensure each nut holding the bus
bars in place are torqued to 20 lb-in). Make sure all wires are clean and bright
to assure good electrical contact.

10.

Open water valve to allow water supply to reach boiler feed mechanism.

11.

As boiler automatically refills, observe the new flange assembly for possible
leaks. If water is noticed, the bolts must be re-tightened. Before doing this, turn
the boiler off at the main fuse safety switch.

12.

When boiler reaches working pressure, check flange assembly again for leaks.

Avoid use of chemical cleaning compounds.
Follow maintenance instructions provided with the boiler.

Torque Values:

Element Flange Bolts: 22 lb-ft

Element Terminals: 20 lb-in

Contactor Terminals: See Torque Chart

For Illustrative Purposes Only.
Power wiring shown in approxi-
mate factory-installed location

Torque

Wrench

Torque Wrench

Torque

Wrench

Boiler with
McDonnell Miller

1

1

2

1” Steam Equalizing Pipe

Pump and Low Water Control

Normal Boiler Water Line

CutOff

 

Level

 

is

 

Arrow

 

Mark

 

Blowdown

 

Valve

1”

 

Water

 

Equalizing

 

Pipe

TORQUE VALUES

Element Flange Bolts

22 lb-ft

Element Terminals

20 lb-in

Contactor Terminals: Tighten to torque

specified on contactor.

Before

 

Installing

 

your

 

new

 

elements

 

be

 

sure

McDonnell

 

Miller

 

low

 

water

 

cutoff

 

and

 

aux.

 

low

 

water

 

cutoff

 

(if

 

supplied)

 

is

 

operating

 

properly.

 

The

 

float

 

chamber

 

and

 

lower

equalizer

 

column

 

of

 

the

 

MM

 

control

 

must

 

be

 

completely

 

clear

 

of

sludge

 

or

 

other

 

foreign

 

matter.

 

Failure

 

to

 

do

 

this

 

may

 

cause

 

the

 

immediate

 

burn-out

 

of

 

the

 

new

 

elements.

 

If

 

the

 

unit

 

is

 

probe

equipped,

 

check

 

condition

 

of

 

the

 

probes

 

and

 

isolator.

All

 

elements

 

are

 

thoroughly

 

checked

 

before

 

shipment.

 

The

 

manu-

facturer

 

cannot

 

be

 

responsible

 

for

 

burn-outs

 

caused

 

by

 

a

 

faulty

 

low

 

water

 

cutoff.

The

 

lower

 

equalizer

 

column

 

can

 

best

 

be

 

examined

 

by

 

breaking

 

the

 

unions

 

on

 

either

 

side

 

and

 

then

 

visually

 

and

 

manually

 

examining

 

the

 

piping

 

with

 

your

 

finger

 

or

 

probes

 

to

 

see

 

if

 

it

 

is

 

clear

 

and

 

clean.

36

Summary of Contents for mr.steam CU Series

Page 1: ...tors Installation Operation Maintenance Manual Models CU360 through CU4500 Installation Operation Maintenance Manual _______________________________________ IMPORTANT LEAVE THIS MANUAL WITH THE OWNER...

Page 2: ...Mechanical Digital Blowdown Timers 28 29 30 Minute Room Timer 30 31 Trouble Shooting 32 34 Check PC Boards Probes Steam Solenoid Valve Digital 1 Control Heating Element 35 Element Replacement Instruct...

Page 3: ...closed with full walls door floor and ceiling 2 It is recommended that a gasketed door be used for heat sealing and steam containment Windows sky lights and the like that are part of the steam room sh...

Page 4: ...Steambath generator is provided with a WARNING sign This WARN ING is to be secured to the outside of the steam room on the steamroom door or adjacent to that door It s location must be such that all...

Page 5: ...n or the like 2 Do NOTinstall steambath generator outdoors or wherev er environmental conditions may effect the safety and or performance of the generator Do NOT install steambath generator in locatio...

Page 6: ...inches Shipping No KW Volume cu ft Size NPT Size NPT W L H Wt lbs CU360 9 400 1 4 1 20 30 38 230 CU500 12 500 1 4 1 20 30 38 230 CU750 18 750 1 4 1 20 30 38 230 CU1000 24 1000 1 4 1 20 30 38 230 CU12...

Page 7: ...ow 1 All dimensions are approximate 2 CU360 to CU1400 have electronic liquid level controls MM150 Liquid Level Control on CU2000 and larger models only 15 7 15 7 22 0 6 6 9 4 13 5 25 0 16 4 12 6 1 9 3...

Page 8: ...ly CU360 to CU1400 have electronic liquid level controls 2 Minimum Clear ance from Combustible Sur faces 1 above top of CU generator Front of CU generator suitable for alcove installation only Type of...

Page 9: ...rea Clearance 36 89 18 36 103 MM150 Service Area Clearance Service Area Clearance 24 180 Max 16 Access to service areas to be supplied by customer Access door must not be less than 30 wide x 78 high R...

Page 10: ...ce as required in accordance with Code 7 Provide unions as required to facilitate installa tion and disconnection of piping 8 Recheck all factory and field plumbing con nections for tightness WATER QU...

Page 11: ...am ooms us ac l c be lass o othe o heat es sta t mate als used o steam oom e closu e stall each steam head 2 ches abo e the loo ocate each steamhead a a om bathe seat a ea a d a a om t a c atte s as e...

Page 12: ...60 167 145 73 58 CU3000 72 200 174 87 70 CU4500 108 300 260 130 104 WIRING To avoid possible electric shock the steambath generator shall be suitably grounded in accordance with National Electric and...

Page 13: ...AGES 14 15 16 FOR DIAGRAMS Installer shall use a safety switch of ade quate capacity employing suitably rated circuit breakers or fuses between main electrical power source s and the generator Locatio...

Page 14: ...d room requires a Digital 1 and Solenoid Valve s CONTROL CIRCUIT WIRING DIAGRAM Digital 1 Temperature Control System and optional automatic blowdown assembly For Models CU360A to CU750A and CU1000AF3...

Page 15: ...00AB3 CU1000AC3 CU1250AB3 CU1250AC3 CU1400AB3 CU1400AC3 1 Larger rooms may require two or more steam solenoid valves in parallel 2 When generator services two rooms second room requires a Digital 1 an...

Page 16: ...the steam room at the location selected by the designer architect DO NOT LOCATE THE DIGITAL 1 and CU HTC SENSORS NEAR OR ABOVE THE STEAMHEAD S AS THIS MAY CAUSE DIRECT STEAM EMISSION TO INTERFERE WIT...

Page 17: ...lves and two steamheads CU2 D1 KIT CONSISTS OF Digital 1 Control factory installed on generator Digital 1 Sensor Two 3 4 Steam Solenoid Valves and 3 4 Steamhead Two Acrylic Shields one for each steamh...

Page 18: ...ided screws and nuts For one room installation use the upper blank 2 Connect the control wires to the bottom of the terminal block above the control The terminals are coded with the wire insulation co...

Page 19: ...will de energize to OFF When steam pressure reaches the operating pressure control setting the pres sure control will de energize the contactor s Operating pressure control is factory set at 5 psig I...

Page 20: ...d AM PM imprints for each day The time switch is set by push ing the captive trippers to the outer ring position for the entire period that the boiler is to be turned ON i e 2 hours to each tripper on...

Page 21: ...e closed Auto blowdown light should be OFF 3 Turn the override switch to permanent ON I On Off Switch pilot light and generator should be OFF Auto blowdown light should be ON Motorized drain valve rem...

Page 22: ...nst touch contact must be ensured by a proper mount ing When fitting the timer make sure that during normal operation it is impossible for the end user of the steam generator it was fitted in to remov...

Page 23: ...o be fully opened Main disconnect switch to be in ON position Generator switch to be in ON position Since generator will be empty water solenoid will be energized allowing the genera tor to fill with...

Page 24: ...switch to the OFF position and close water supply valve De energize wall mount ed safety switch Open blowdown valve s SLOWLY Pressure may still be in the generator 2 Discharge is complete when gauge g...

Page 25: ...INTENANCE INSTRUCTIONS To establish a good preventive maintenance program we suggest that the site equipment foreman engineer or owner operator familiarize themselves with these guidelines 1 Daily blo...

Page 26: ...d the glass outlet is pointing directly upward Verify top and bottom fit tings are threaded into the tapping the same number of turns distance A distance B 3 Remove glass packing nut friction washer d...

Page 27: ...to keep glass clean Use diluted acids such as Hydrochloric muriatic acid when regular cleaners do not seem to work Do not use wire brushes or any other abrasive materials which could scratch the glass...

Page 28: ...Due to the timer having one tripper for every 2 hours the boiler will need to be OFF a minimum 2 hours If less down time is needed the digital timer PN 103662 can be set to the minute SETTING TIME To...

Page 29: ...lay the boiler is currently running and if OFF is indicated the boiler is off blowing down Once one of the programs are started the indicator will automatically turn to the ON position and when one of...

Page 30: ...mercial Steambaths Electronic Interval Timer for MrSteam CU Commercial Steambaths Installation and Operating Manual 30 FUNCTIONALITY OF THE TIMESWITCH During the preset running time the timer energize...

Page 31: ...After the preset running time has elapsed the timer switches the connected steam solenoid off issuing short beeps for up to 15 seconds The value 0 00 is shown on the display and the colon stops flash...

Page 32: ...eating element Contactor chatters Defective PC board Check replace PC Board Generator floods Water feed solenoid Reverse solenoid connection installed backwards CU360 1400 Port 1 towards generator 2 t...

Page 33: ...Substitution of components or modification of wiring systems voids warranty and can lead to dangerous oper ating conditions Pulling off the purple wire from the board should cause the water solenoid...

Page 34: ...release pressure to zero 0 psig before resuming operation of steam bath generator STEP 8 Check to see that you have 120V at the contactor If you do not then one of your pressure controllers are trippe...

Page 35: ...e control voltage ON and turn the boiler switch ON Measure the voltage across L1 and L2 on the 104460 board The voltage should be approximately 110 VAC 2 On the 104460 board disconnect the wire from t...

Page 36: ...to a torque listed on the contactor ensure each nut holding the bus bars in place are torqued to 20 lb in Make sure all wires are clean and bright to assure good electrical contact 10 Open water valve...

Page 37: ...J Safety Valve K On Off Switch L Mechanical low water cutoff and feeder MM150 M Auxiliary low water cutoff probe LABEL FUNCTION CU360 1400 Typical Component Arrangement Front Right Side CU2000 4500 w...

Page 38: ..._______________________________________________________ ELECTRIC cont ________________________________________________________________________________ 99317 Fuse Block 480V ___________________________...

Page 39: ...____________ PRESSURE CONTROL _________________________________________________________ 99113R Operating Pressure Control 0 15 PSIG _________________________________________________________ 99290 Pres...

Page 40: ...A 90301 1 800 72 STEAM 2021 Mr Steam and des AirTempo AromaFlo AutoFlush AutoSteam AudioWizard Butler Package ChromaSteam Clean Steam Every Time Club Therapy Digital 1 Express Steam From Bathroom to S...

Reviews: