background image

mr

.

steam

®

C U S E R I E S

Installation, Operating & Maintenance Manual

4.

Generators

 

equipped

 

with

 

level

 

probes

 

(Models

 

CU360

 

-1400)

 

for

 

maintaining

 

operating

 

water

 

level

 

and

 

probe

 

for

 

auxiliary

 

low

 

water

 

cutoff

 

protection

 

need

 

special

 

consideration.

 

The

 

probe

 

should

 

be

 

checked

 

for

 

chemi-

cal

 

deposits

 

and

 

cleaned

 

as

 

necessary.

 

This

 

should

 

be

 

done

 

every

 

three

 

months

 

or

 

sooner

,

 

as

 

required

 

by

 

usage

 

and/or

 

water

 

quality.

The

 

probes

 

and

 

probe

 

isolators

 

should

 

be

 

cleaned

 

using

 

the

 

following

 

procedure:

a.

Use

 

emery

 

paper

 

to

 

clean

 

probes.

b.

Remove

 

the

 

probe

 

isolators.

c.

Use

 

a

 

bottle

 

brush

 

to

 

remove

 

scale

 

from

 

the

 

inside

 

of

 

the

 

probe

 

isolators.

 

Care

 

must

 

be

 

taken

 

to

 

ensure

 

the

 

two

 

holes

 

on

 

the

 

side

 

of

 

the

 

probe

 

isolators

 

are

 

clear.

d.

Flush

 

probe

 

isolator

 

thoroughly

 

with

 

water.

e.

Use

 

Teflon

 

tape

 

on

 

probe

 

isolator

 

threads

 

and

 

rein-

stall.

 

Use

 

Teflon

 

tape

 

on

 

probe

 

threads

 

and

 

reinstall.

f.

After

 

installation,

 

make

 

sure

 

the

 

probe

 

is

 

not

 

touching

 

ground.

 

With

 

the

 

generator

 

drained

 

and

 

probe

 

wires

 

disconnected,

 

there

 

should

 

be

 

no

 

continuity

 

between

 

the

 

probe

 

and

 

ground.

Under any circumstances,

only qualified

service personnel should attempt the above procedures.
Always insure all electrical power supplies are disconnect-
ed at the main disconnect switches to prevent electric
shock. Always insure that pressure within steam generator
is 0 PSIG (zero pressure) whenever plumbing connections,
including any factory-plumbed components, are being dis-
connected.

5. Torque Values

Every two months or more frequently

if required, insure all element flange bolts, element
terminals, and contactor terminals are tightened to the
following specifications.

See page 36 for additional

information and illustrations.

MAINTENANCE INSTRUCTIONS

To establish a good preventive maintenance
program, we suggest that the site equipment
foreman, engineer or owner/operator familiarize
themselves with these guidelines:

1. Daily blowdown

at max 5 PSIG operating pressure

is recommended for best steambath generator per-
formance. In order to safeguard the heating ele-
ment(s) within the steambath generator, the main
wall switch and the steambath generator switch
shall both be placed in the OFF position

prior to

blowing down the generator.

Blowdown instruc-

tion should then be followed as outlined in this
manual.

Do not

use chemical cleaning compounds

in the steambath generator since the chemical
agents may damage some of the generator compo-
nents. A daily blowdown will assist in prolonging
product operation.

2. Only after electric power supplies have been

disconnected at main disconnect switch, a
monthly inspection

- should be made of all wiring.

All electrical connections should be checked for
tightness. A check for steam and/or water leaks
should be made and any loose fittings must be
tightened immediately. Check heating element
flange bolts for tightness between preventative
maintenance service Specific torque in 22 Ft. lbs.
cold.

3.

Generators equipped with the McDonnell-Miller

control (Models CU2000 and larger), should be
checked for proper operation

every three months

or sooner.

At the same time, a bottom heating ele-

ment should be removed and inspected. If scale
has begun to form, all elements should be cleaned
and re-installed, using only new gaskets and bolts.
The pressure control should also be removed to
insure that the bellows has not become clogged.
(See trouble-shooting guide for instructions.) Check
valves should be inspected for leakage and proper
operation.

TORQUE VALUES

Element Flange Bolts

22 lb-ft

Element Terminals

20 lb-in

Contactor Terminals : Tighten to

torque specified on contactor.

25

Summary of Contents for mr.steam CU Series

Page 1: ...tors Installation Operation Maintenance Manual Models CU360 through CU4500 Installation Operation Maintenance Manual _______________________________________ IMPORTANT LEAVE THIS MANUAL WITH THE OWNER...

Page 2: ...Mechanical Digital Blowdown Timers 28 29 30 Minute Room Timer 30 31 Trouble Shooting 32 34 Check PC Boards Probes Steam Solenoid Valve Digital 1 Control Heating Element 35 Element Replacement Instruct...

Page 3: ...closed with full walls door floor and ceiling 2 It is recommended that a gasketed door be used for heat sealing and steam containment Windows sky lights and the like that are part of the steam room sh...

Page 4: ...Steambath generator is provided with a WARNING sign This WARN ING is to be secured to the outside of the steam room on the steamroom door or adjacent to that door It s location must be such that all...

Page 5: ...n or the like 2 Do NOTinstall steambath generator outdoors or wherev er environmental conditions may effect the safety and or performance of the generator Do NOT install steambath generator in locatio...

Page 6: ...inches Shipping No KW Volume cu ft Size NPT Size NPT W L H Wt lbs CU360 9 400 1 4 1 20 30 38 230 CU500 12 500 1 4 1 20 30 38 230 CU750 18 750 1 4 1 20 30 38 230 CU1000 24 1000 1 4 1 20 30 38 230 CU12...

Page 7: ...ow 1 All dimensions are approximate 2 CU360 to CU1400 have electronic liquid level controls MM150 Liquid Level Control on CU2000 and larger models only 15 7 15 7 22 0 6 6 9 4 13 5 25 0 16 4 12 6 1 9 3...

Page 8: ...ly CU360 to CU1400 have electronic liquid level controls 2 Minimum Clear ance from Combustible Sur faces 1 above top of CU generator Front of CU generator suitable for alcove installation only Type of...

Page 9: ...rea Clearance 36 89 18 36 103 MM150 Service Area Clearance Service Area Clearance 24 180 Max 16 Access to service areas to be supplied by customer Access door must not be less than 30 wide x 78 high R...

Page 10: ...ce as required in accordance with Code 7 Provide unions as required to facilitate installa tion and disconnection of piping 8 Recheck all factory and field plumbing con nections for tightness WATER QU...

Page 11: ...am ooms us ac l c be lass o othe o heat es sta t mate als used o steam oom e closu e stall each steam head 2 ches abo e the loo ocate each steamhead a a om bathe seat a ea a d a a om t a c atte s as e...

Page 12: ...60 167 145 73 58 CU3000 72 200 174 87 70 CU4500 108 300 260 130 104 WIRING To avoid possible electric shock the steambath generator shall be suitably grounded in accordance with National Electric and...

Page 13: ...AGES 14 15 16 FOR DIAGRAMS Installer shall use a safety switch of ade quate capacity employing suitably rated circuit breakers or fuses between main electrical power source s and the generator Locatio...

Page 14: ...d room requires a Digital 1 and Solenoid Valve s CONTROL CIRCUIT WIRING DIAGRAM Digital 1 Temperature Control System and optional automatic blowdown assembly For Models CU360A to CU750A and CU1000AF3...

Page 15: ...00AB3 CU1000AC3 CU1250AB3 CU1250AC3 CU1400AB3 CU1400AC3 1 Larger rooms may require two or more steam solenoid valves in parallel 2 When generator services two rooms second room requires a Digital 1 an...

Page 16: ...the steam room at the location selected by the designer architect DO NOT LOCATE THE DIGITAL 1 and CU HTC SENSORS NEAR OR ABOVE THE STEAMHEAD S AS THIS MAY CAUSE DIRECT STEAM EMISSION TO INTERFERE WIT...

Page 17: ...lves and two steamheads CU2 D1 KIT CONSISTS OF Digital 1 Control factory installed on generator Digital 1 Sensor Two 3 4 Steam Solenoid Valves and 3 4 Steamhead Two Acrylic Shields one for each steamh...

Page 18: ...ided screws and nuts For one room installation use the upper blank 2 Connect the control wires to the bottom of the terminal block above the control The terminals are coded with the wire insulation co...

Page 19: ...will de energize to OFF When steam pressure reaches the operating pressure control setting the pres sure control will de energize the contactor s Operating pressure control is factory set at 5 psig I...

Page 20: ...d AM PM imprints for each day The time switch is set by push ing the captive trippers to the outer ring position for the entire period that the boiler is to be turned ON i e 2 hours to each tripper on...

Page 21: ...e closed Auto blowdown light should be OFF 3 Turn the override switch to permanent ON I On Off Switch pilot light and generator should be OFF Auto blowdown light should be ON Motorized drain valve rem...

Page 22: ...nst touch contact must be ensured by a proper mount ing When fitting the timer make sure that during normal operation it is impossible for the end user of the steam generator it was fitted in to remov...

Page 23: ...o be fully opened Main disconnect switch to be in ON position Generator switch to be in ON position Since generator will be empty water solenoid will be energized allowing the genera tor to fill with...

Page 24: ...switch to the OFF position and close water supply valve De energize wall mount ed safety switch Open blowdown valve s SLOWLY Pressure may still be in the generator 2 Discharge is complete when gauge g...

Page 25: ...INTENANCE INSTRUCTIONS To establish a good preventive maintenance program we suggest that the site equipment foreman engineer or owner operator familiarize themselves with these guidelines 1 Daily blo...

Page 26: ...d the glass outlet is pointing directly upward Verify top and bottom fit tings are threaded into the tapping the same number of turns distance A distance B 3 Remove glass packing nut friction washer d...

Page 27: ...to keep glass clean Use diluted acids such as Hydrochloric muriatic acid when regular cleaners do not seem to work Do not use wire brushes or any other abrasive materials which could scratch the glass...

Page 28: ...Due to the timer having one tripper for every 2 hours the boiler will need to be OFF a minimum 2 hours If less down time is needed the digital timer PN 103662 can be set to the minute SETTING TIME To...

Page 29: ...lay the boiler is currently running and if OFF is indicated the boiler is off blowing down Once one of the programs are started the indicator will automatically turn to the ON position and when one of...

Page 30: ...mercial Steambaths Electronic Interval Timer for MrSteam CU Commercial Steambaths Installation and Operating Manual 30 FUNCTIONALITY OF THE TIMESWITCH During the preset running time the timer energize...

Page 31: ...After the preset running time has elapsed the timer switches the connected steam solenoid off issuing short beeps for up to 15 seconds The value 0 00 is shown on the display and the colon stops flash...

Page 32: ...eating element Contactor chatters Defective PC board Check replace PC Board Generator floods Water feed solenoid Reverse solenoid connection installed backwards CU360 1400 Port 1 towards generator 2 t...

Page 33: ...Substitution of components or modification of wiring systems voids warranty and can lead to dangerous oper ating conditions Pulling off the purple wire from the board should cause the water solenoid...

Page 34: ...release pressure to zero 0 psig before resuming operation of steam bath generator STEP 8 Check to see that you have 120V at the contactor If you do not then one of your pressure controllers are trippe...

Page 35: ...e control voltage ON and turn the boiler switch ON Measure the voltage across L1 and L2 on the 104460 board The voltage should be approximately 110 VAC 2 On the 104460 board disconnect the wire from t...

Page 36: ...to a torque listed on the contactor ensure each nut holding the bus bars in place are torqued to 20 lb in Make sure all wires are clean and bright to assure good electrical contact 10 Open water valve...

Page 37: ...J Safety Valve K On Off Switch L Mechanical low water cutoff and feeder MM150 M Auxiliary low water cutoff probe LABEL FUNCTION CU360 1400 Typical Component Arrangement Front Right Side CU2000 4500 w...

Page 38: ..._______________________________________________________ ELECTRIC cont ________________________________________________________________________________ 99317 Fuse Block 480V ___________________________...

Page 39: ...____________ PRESSURE CONTROL _________________________________________________________ 99113R Operating Pressure Control 0 15 PSIG _________________________________________________________ 99290 Pres...

Page 40: ...A 90301 1 800 72 STEAM 2021 Mr Steam and des AirTempo AromaFlo AutoFlush AutoSteam AudioWizard Butler Package ChromaSteam Clean Steam Every Time Club Therapy Digital 1 Express Steam From Bathroom to S...

Reviews: