GENERAL ELECTRICAL & GROUNDING
DANGER:
Improper or faulty hookup of electrical components in the
display case can result in severe injury or death.
SELF CONTAINED
MODEL
VOLTAGE
PERMANENT CONNECTED AMPS
CORD CONNECT AMPS/CORD PLUG
ITR3626 & ITR3634
120V/60H/1PH
MIN CIRCUIT AMPACITY 13.9/ MAX FUSE SIZE 20
TOTAL AMPS 8.7 / 5-15
ITR4826 & ITR4834
120V/60H/1PH
MIN CIRCUIT AMPACITY 16.9/ MAX FUSE SIZE 20
TOTAL AMPS 10.7 / 5-15
ITR6026 & ITR6034
120V/60H/1PH
MIN CIRCUIT AMPACITY 17.3/ MAX FUSE SIZE 20
TOTAL AMPS 11.0 / 5-15
REMOTE
MODEL
VOLTAGE
PERMANENT CONNECTED AMPS
ITR3626 & ITR3634
120V/60H/1PH
MIN CIRCUIT AMPACITY 15/ MAX FUSE SIZE 15
ITR4826 & ITR4834
120V/60H/1PH
MIN CIRCUIT AMPACITY 15/ MAX FUSE SIZE 15
ITR6026 & ITR6034
120V/60H/1PH
MIN CIRCUIT AMPACITY 15/ MAX FUSE SIZE 15
Permanent Connected
-Only a licensed electrician must perform all case electrical connections.
-All electrical wiring hookups must be done in accordance with all applicable local, regional, or national
electrical standards.
-A separate circuit for each display case is required to prevent other appliances on the same circuit from
overloading the circuit and causing malfunction.
-The electrical service must be grounded upon installation.
-See the electrical data plate located at the rear of the case for proper circuit size and wire ampacity.
-The electrical connection box is accessible from the rear of the case with rear grill removed. See grill
removal section of this manual for grill removal procedure.
Floor Models:
FIELD CONNECTION BOX
FLOOR CONDUIT
CONNECTION .875
O
FLOOR CONDUIT
CONNECTION .875
O
CONDUIT OR
POWER CORD
CONNECTION .875