Pump Assembly Continued
Inlet Piping
Keep the inlet pipe free of high points which could trap air and could disrupt pump priming. Vac-
uum and/or pressure gages are recommended to allow measurement of pump inlet pressure.
NEVER throttle the pump on the inlet side.
Outlet Piping
The pump discharge piping should have a removable section of pipe such as a spool piece or
elbow to allow the pump to slide forward for service. Servicing the shaft seal, water bearing or
flexible coupling requires a space of approximately 30.5 cm (12 inches) minimum. The pump as
-
sembly must be free to move away from the motor in order to gain access to these components.
REMOVABLE SECTIONS
FOR PUMP SERVICE
OUTLET PIPING
DISCHARGE HOUSING
30.5 cm
(12 in)
MINIMUM
OR
Figure 96 -
Removable Section
For Pump Service