System Manual | 2013
VAIE 2000 | Voice Alarm Integrated Systems
VAC 2006 • VAR 2006
UK
Label
Part being diagnosed
display
Cause
Action required
All
All
Ok
No failure
-
N.T.
Diagnostics disabled during
configuration (see Set>
BACkGROUND TEST menu)
-
Res.
Failure (Fault signal) cleared
Access the Report> FAULTS panel from the
OPERATOR menu and carry out a MANUAL
RESET of the FAILURE signal.
1-Local emerg.
Hand-held microphone or
Emergency Push-button.
Fault
Failure of hand-held microphone
or of Emergency Push-button.
Make sure that the microphone has been
correctly plugged into the socket on the front
panel. If the failure persists, contact the Service
Centre.
2-Configuration
SD card
Fault
SD card error or error in reading
messages.
Make sure that the SD card has been correctly
plugged into its slot on the rear panel of the
controller.
3-Emerg. Unit
Emergency
microphone stations
Fault
Failure of at least one
emergency microphone station.
Make sure that the microphone of the station
is correctly plugged in.
If the failure persists,
contact the Service Centre.
4-Messages
Recorder/player of the
emergency EVAC and ALERT
message
Fault
Presence of two or more failures.
Make sure that the SD card has been correctly
plugged into its slot on the rear panel of the
controller.
5-Line connect.
CAT5 connection to:
- DPU
- VAR
- AMP
Fault
Communication error.
Check the connections.
If the failure persists,
contact the Service Centre.
6-Remote Link
Intercommunication with
remote VAC 2006 units
Fault
Press key
6
to access the dedicated “LINk
FAULTS” panel. Check the connecting cables
between the VAC 2006 units for connection
VAC 2006 LINk.
If the failure persists, contact the Service
Centre.
Tab. 8.4.1.3