8.3.4 InPut 2
Management of the source on the In 2 input
Hold the numerical key associated with the function down and turn the +/-
knob to adjust the setting.
•
1-Mode
: Setting of the operating mode of the input for using the
voice
channel as a PA Source.
Hold key
1
(Mode) down and turn the +/- knob to select the
required mode from among the following:
>
on
:
The input will be connected directly as a voice source and will
be operational on the basis of the priority and of the zone list
that is selected.
The RESET, ALERT, EVAC, MENU and Ok have no functions.
Press ESC to return to the AUDIO SETTINGS menu.
>
VoX lev. 1÷7
:
This input is set as a voice source with automatic precedence activated by the presence of the incoming audio signal. The
precedence is activated when the audio signal exceeds the threshold level that has been set. It is possible to choose from
among seven increasing threshold levels. Careful adjustment of the threshold will enable prompt broadcasting of the signal to be
achieved, avoiding involuntary activation of precedence by noise induced on the cable.
>
Precedence
:
The input is enabled for broadcasting as a voice source by closure of a contact connected to the precedence terminals.
>
off
: input disabled for the PA announcement function. The source connected continues to be available for selection as a BGM
Source.
•
2-Zone call
: Setting the operating mode of the input for using the voice channel as a PA source. Hold down key
2
(Zone call) then turn the
+/- knob to select the required mode from among the following options:
>
Z. 1 ÷ Z. 216
: To select the specific zone in which you wish to broadcast the calls/music.
>
All
:
To broadcast the calls/music to all the zones in the system.
>
C. 1 ÷ Z. 64
:
To select a pre-established group of zones (these configurations can be created using the controller.exe
software) in which to broadcast the calls/music.
•
3-Hold on:
To set the release time after an input signal, when the VOX mode is selected.
Hold down key
3
(Hold on) then turn the +/- knob to choose a time (between 1 and 99 secs.).
•
4-Priority:
Priority assigned to an input when it is used as a voice source for service announcements. There are 7 priority levels. The input can
be muted by another voice source featuring a higher level of priority. Hold down key
4
(Priority) then turn the +/- knob to choose the
required level.
•
5-Sensitivity:
Adjustment of sensitivity. Press key
5
(Sensitivity) to choose the required level (between 0, 6, 12 or 18 dB).
•
6-Phantom:
Setting of the Phantom power supply (OFF = not active / ON = active). To change the setting, press key
6
(Phantom), then release
it.