System Manual | 2013
VAIE 2000 | Voice Alarm Integrated Systems
3
VAC 2006 • VAR 2006
UK
• Configuring the standby amplifiers
From the menu, select
View > Spare configuration
to open a complete schedule of all the amplifiers
installed in the system.
In the window, the left-hand column shows
the DPU amplifiers entered previously in the
configuration file as standby units. For each of
these, it is possible to indicate the amplifiers they
will replace in the event of a failure. To do this,
select the amplifier in the drop-down menu and
click on ‘
Add
’ to associate it with its standby unit.
Once you have loaded the file, you can indicate
whether it is a message to be sent in warning
situations (Alert) or in evacuation situations
(Evac).
It is also possible to add a brief description of
each message entered (max 25 digits).
In addition to voice messages, a warning tone
(Chime) can also be entered, using the same
procedure.
Press
End
to save the configuration, or press
Canc
. to cancel it and return to the main window.
• Compiling voice messages / warning signals
From the menu, select
View > Message Compiler
to open the window enabling management of the pre-recorded voice messages and of the
warning signal, if any. Click on
Path > Add file
and load the required *.wav file.
n.B.. the files to be used must necessarily be recorded in and /or converted into the *.WAV 48 ksample 16bit audio format.
Once you have completed configuring CONTROLLER 0, save the project and click on the “CONTROLLER 1” tab to proceed with its
configuration.