System Manual | 2013
VAIE 2000 | Voice Alarm Integrated Systems
VAC 2006 • VAR 2006
UK
5.2.2 VAR 2006 Router
Front panel
F4.
FAuLtS LEds
The FAULT LEDs provide the following information:
• COM-SYS
Flashing indicates the absence of a connection with the controller.
• CTRL IN
This indicates a failure of the controlled inputs.
• MAINS
This indicates a failure of the internal power supply.
• BATTERY
This indicates the lack of power from the battery.
• GND
Ground Fault.
• SP. Z1-3
Failure of the amplifier connected to zones Z1 to Z3.
• SP. Z4-6
Failure of the amplifier connected to zones Z4 to Z6.
• MUS.-SPARE Failure of the music/spare amplifier.
F5.
StAtuS LEds
The STATUS LEDs provide the following information:
• ALARM
This indicates the presence of a (generic) emergency voice and/or recorded message being sent out.
• CTRL IN
This indicates the presence of a emergency voice and/or recorded message from one of the input contacts being sent out.
• DISABLE
This indicates the presence of at least one zone for which broadcasting of emergency messages is not envisaged.
• FAULT
This indicates the presence of a failure on at least one of the 6 output lines.
F6.
ZonE outPut LEds
The red
MSG
LEDs indicate in real time the zone(s) in which the emergency voice signal is being broadcast:
Flashing
Warning message being sent out.
Steady ON
Evacuation or live message being sent out.
The yellow
LInE A/B
LEDs indicate the following:
Flashing
Zone failure: impedance measured on the zone is out of specifications.
Steady ON
This indicates the zones in which broadcasting of emergency messages is not envisaged (DISABLE function).
F7.
PRoGRAM InSERtIon
The LEDs indicate the following:
Flashing
The zone in which a broadcast call (NOT an emergency call) is being sent out.
Steady ON
Background music is activated for this zone (this function is only possible if there is also an amplifier MUS.-SPARE).
The push-buttons allow background music to be activated in the corresponding zones (this function is only possible if there is also a
MUS.-SPARE amplifier).
F8.
Status LEds
Power supply/call status LEDs:
• EMERG.
This indicates that the system is in a state of emergency.
• CALL
This indicates that a broadcast call is being sent out.
• ON
This indicates the presence of the 230 VAC power supply.
• BATT.
This indicates the presence of the 24 VDC external power supply.