-32-
Input Range: -5 ~ 5[V]
9.2.2
When the Input Range value is 1, the range of analog input is -5 ~ 5[V] in Voltage Input Mode. The analog input
signals are converted to digit data -4096 ~ 4095 (Full Scale). If the input signal is out of range, it is converted to
the minimum or maximum data.
Every 1[V] of the analog signal is converted to 819.2 digital data data (After the conversion, the decimal places
are removed).
Table 9-4. Data Conversion for Input Range -5 ~ 5[V]
Figure 9-2. Data Conversion for Input Range -5 ~ 5[V]
Input Range
Converted Data
1 (-5 ~ 5[V])
-4096 ~ 4095 (-5 ~ 5[V])