-34-
Input Range: 0 ~ 10[V]
9.2.4
When the Input Range value is 3, the range of analog input is 0 ~ 10[V] in Voltage Input Mode. The analog input
signals are converted to digit data 0 ~ 8191 (Full Scale). If the input signal is out of range, it is converted to the
minimum or maximum data.
Every 1[V] of the analog signal is converted to 819.2 digital data data (After the conversion, the decimal places
are removed).
Table 9-6. Data Conversion for Input Range 0 ~ 10[V]
Figure 9-4. Data Conversion for Input Range 0 ~ 10[V]
Input Range
Converted Data
3 (0 ~ 10[V])
0 ~ 8191 (0 ~ 10[V])