-21-
6.2
Setting Current Input Mode
To use Ezi-IO EtherCAT AD in Current Input Mode, set DIP switches as the
Figure 6-3
.
If you use any channel in Current Input Mode, select the SDO Communication for setting method (SW3.1=OFF).
(Example) Setting Channel 2
①
Set LSET switch (SW3.1) of INPUT RANGE to OFF before supplying power to the module.
②
Set Channel 2 to Current Input Mode with the Input Mode Selection Switch (SW4.2=ON) before
supplying power to the module.
③
Connect the analog input signal and ground to the pin 2 and GND of Input Connector (CN2).
Figure 6-3. Setting Current Input Mode