-33-
Input Range: -2.5 ~ 2.5[V]
9.2.3
When the Input Range value is 2, the range of analog input is -2.5 ~ 2.5[V] in Voltage Input Mode. The analog
input signals are converted to digit data -4096 ~ 4095 (Full Scale). If the input signal is out of range, it is
converted to the minimum or maximum data.
Every 1[V] of the analog signal is converted to 1638.4 digital data data (After the conversion, the decimal places
are removed).
Table 9-5. Data Conversion for Input Range -2.5 ~ 2.5[V]
Figure 9-3. Data Conversion for Input Range -2.5 ~ 2.5[V]
Input Range
Converted Data
2 (-2.5 ~ 2.5[V])
-4096 ~ 4095 (-2.5 ~ 2.5[V])