MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
63
B. System Troubles
ENTRY INDICATES
AC Trouble
AC input low or off
AddrLp 1 DBLSHT
Double short trouble on addressable loop 1
AddrLp 1 OPEN
Open circuit trouble on addressable loop 1
AddrLp 1 SHORT
Short circuit trouble on addressable loop 1
BATT Trouble
Battery input low or off
CITY Trouble
Local Energy circuit open
DACT Acct Trb
DACT account reporting trouble
DACT Com Trouble
DACT communication trouble with main processor
DACT PL x Trouble
Open or short on DACT phone line x
FLASH FATAL Trb
Configuration Flash memory trouble
GRND FAULT Trbl
Ground Fault trouble
LCDxx NoRespons
LCD Annunciator xx programmed but is not responding
LCDxx Not Pgmd
LCD Annunciator xx is not programmed but is responding
LCDxx Trouble
LCD Annunciator xx reports trouble
MNLP Bad Msg
Main processor to loop processor communication trouble
MNLP Fifo Xmit
Main processor to loop processor communication trouble
MNLP NoRespons
Main processor to loop processor communication trouble
NACxx Trouble
NAC xx wiring is open or shorted
PC Pgmr Trb
Control unit is not receiving communication from PC
QuickTest Abort
Quick Test Timer expired causing abnormal exit of Quick Test
Trb Reminder
Trouble Reminder timer expired