MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
55
Auxiliary Module Battery Calculations
Panel and Module Current
Standby Current (A)
Alarm Current (A)
RDC-2 Remote
Standby 0.020
X =
+
NA
Annunciator
Alarm 0.085
X =
NA
+
SRU-2 Serial
Standby 0.032
X =
+
NA
Relay Unit
Alarm 0.192
X =
NA
+
SRE-8 Serial
Standby 0.000
X =
+
NA
Relay Extender
Alarm 0.160
X =
NA
+
SLU-2 Serial
Standby 0.018
X =
+
Annunciator Unit
Alarm (Note 5) 0.040
X =
NA
+
SLE-16 Serial
Standby 0.005
X =
+
Annunciator
Extender
Alarm (Note 5) 0.000
X =
NA
+
Total Auxiliary
Module Current
Place these totals in the Total System Current table
Go to Device Current Calculations
Device Current Calculations
Device Current
Catalog #
Quantity
X Current (A)
Standby Current (A) Alarm
Current (A)
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
4-wire Smoke Detectors
Catalog #
Quantity
X Current (A)
Standby
X =
+
NA
Alarm
X =
NA
+
Standby
X =
+
NA
Alarm
X =
NA
+
End of Line Relay
Catalog #
Quantity
X Current (A)
X =
+
+
Notification Appliances
Catalog #
Quantity
X Current (A)
X =
NA
+
X =
NA
+
X =
NA
+
X =
NA
+
Other =
+
+
TOTAL DEVICE Current
Place these totals in the Total System Current table
Go to Total System Current Calculations