MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
39
Primary And Secondary Power Wiring
The AC main connections (TB1) and the battery connections (J4) must be made along the left-
hand side of the main termination board (P/N MPC6-MB or MCP7-MB). Route all high voltage
and non-power limited wiring together and away from power limited wiring. Use the battery
calculation chart to determine battery size.
TX-1
BAT.
B-
B+
GND
N
AC
AC
N
GND
Status Relays And Auxiliary Power Outputs Wiring
The right side of the main board provides for connection of status relay contacts and auxiliary
power connections (TB5-8). Four relays with dry contacts are provided. These contacts are
programmable to alarm, pre-alarm, trouble and supervisory indications. The relay contacts are
Form C and are rated 1A @ 28VDC resistive.
The right-hand edge of the main termination board (TB9) provides for resettable and non-
resettable auxiliary power connections.
Circuit
NAC
Relay Circuit 4
Programmable
Programmable
Relay Circuit 3
Programmable
Relay Circuit 2
Programmable
Relay Circuit 1
Supervised
120 VAC 60Hz
2.4A Max MPC-6000 / RND-2
3.2A Max MPC-7000
Non-Power Limited
Auxiliary Power Outputs
0.4A max. @24VDC nominal
Supervised, Power Limited
Maximum current of all auxiliary
outputs circuits, Serial Interface
Circuit and option boards is:
0.5A for the MPC-6000/RND-2
1.0A for the MPC-7000
Status Relay Contacts
(Shown in normal
standby condition)
1A 28VDC max Resistive
For connection to a
Power Limited Source,
Supervised
C – Common
NO – Normally Open
NC – Normally Closed
Battery Connections
Supervised
Non-Power Limited
For MPC-6000
24V Battery Set (7 to 38.5AH)
For MPC-7000
24V Battery Set (7 to 38.5AH)
(up to 100 AH if HBC-1 Battery
Charger is used)
For RND-2
24V Battery Set (7 to 38.5AH)
Keep All Non-Power Limited Wiring
Separate from Power Limited Wiring