MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
40
MPC-6000 System Power Requirements (Does not include NAC power)
Device Item
Max.(Amps)
MPC-
6000
Amps
MPC-6000 Control Unit (Includes 1 FDLC)
0.190
0.190
Addressable Device Circuit Power
# of Devices X 0.0018 Amps
Auxiliary Power Outputs *
Depends on devices installed
CT-1K City Tie Board
0.055
MPC-DACT DACT Board
0.054
RDC-2 Remote LCD Annunciator *
0.085
SRU-2/SRE-8 Serial Relay Unit *
0.032+0.020 A for each relay
SLU-2/SLE-16 Serial Annunciator Unit *
0.070+ load of each LED or lamp
Total current requirements
Must be less than or equal to
0.75
RND-2 System Power Requirements
Device Item
Max.(Amps)
RND-2
Amps
RND-2 Control Unit (No FDLC)
0.090
0. 090
Auxiliary Power Outputs *
Depends on devices installed
CT-1K City Tie Board
0.055
MPC-DACT DACT Board
0.054
RDC-2 Remote LCD Annunciator *
0.085
Total current requirements
Must be less than or equal to
0.75
MPC-7000 System Power Requirement (Does not include NAC power)
Device Item
Max.(Amps)
MPC-
7000
Amps
MPC-7000 Control Unit (Includes 2 FDLCs) 0.500
0.500
FDLC Loop Driver Board
0.100 x # of FDLCs on LEM-1
NEM-1 Signal Expansion Board
0.250
0.250
LEM-1 Loop Expansion Board
0
0
HBC-1 Battery Charger
1
0
0
Addressable Device Circuit Power
# of Devices X 0.0018 Amps
Auxiliary Power Outputs *
Depends on devices installed
CT-1K City Tie Board
0.055
MPC-DACT DACT Board
0.054
RDC-2 Remote LCD Annunciator *
0.085
SRU-2/ SRE-8 Serial Relay Unit *
0.032+0.020 A for each relay
SLU-2/ SLE-16 Serial Annunciator Unit *
0.070+ load of each LED or lamp
Total current requirements
Must be less than or equal to
3.22
1
Does not include charging current of 1.9A for a fully discharged battery.