MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
53
BATTERY SIZE CALCULATIONS
MPC-6000 Current Calculations
Panel and Module Current
Standby Current (A)
Alarm Current (A)
MPC-6000 Control Unit (includes one loop driver board)
0.190
0.190
Standby
0.005
+
+
CT-1K City Tie
Alarm (Table 1)
NA
+
Standby
0.038
+
NA
MPC-DACT DACT
Board
Alarm
0.054
NA
+
Total Panel
currents
Place these totals in the Total System Current Table
Go to Auxiliary Module Current calculations
RND-2 Current Calculations
Panel and Module Current
Standby Current (A)
Alarm Current (A)
RND-2 Control Unit (no loop driver board)
0.090
0.090
Standby
0.005
+
+
CT-1K City Tie
Alarm (Table 1)
NA
+
Standby
0.038
+
NA
MPC-DACT DACT
Board
Alarm
0.054
NA
+
Total Panel
currents
Place these totals in the Total System Current Table
Go to Auxiliary Module Current calculations
MPC-7000 Current Calculation
Panel and Module Current
Standby Current (A)
Alarm Current (A)
MPC-7000 Control Unit (includes two loop driver boards)
0.450
0.500
CT-1K City Tie
Standby
0.005
+
+
Alarm (Table 1)
NA
+
FDLC Loop
Standby 0.100
X
N/A
Driver (on LEM-1)
Alarm 0.100 X
N/A
HBC-1 Standby
1
0
0 N/A
Loop Expander Bd.
Alarm 0
N/A
0
NEM-1
Standby 0.015
0.015 N/A
NAC Expander Bd.
Alarm 0.250
N/A
0.250
MPC-DACT DACT
Standby 0.038
+
NA
Board
Alarm 0.054
NA
+
Total Panel
currents
1
Does not include charging current of 1.9A for a fully discharged battery.
Place totals in the Total System Current table
Go to Auxiliary Module Current calculations