Smoke alarm 

«CV212-12», «CV212-12-01 » 

425232.003-01 РЭ 

Instruction Manual 

 
 

 

INTRODUCTION 

 

The  Instruction  Manual  is  designed  to  study 

the 

structure, 

functioning 

and 

operating 

procedures  of  the  Smoke  Alarm  CV212-12  and 
CV212-12-01 (hereinafter referred to as Alarm). 
 

The  Alarm  meets  the  requirements  of  EN-

14604. 

1  INTENDED USE 

1.1 

The Alarm is designed to detect the fire, 

accompanied  by  smoke  generation,  as  well  as 
issue audible and light signals of fire alert. 

1.2

 

The Alarm can be operated: 

-  as stand alone; 
-  in  stand  alone  fire  alarm  network  when 
Alarms  are  combined  into  a  group  with  two-
wire lines. 

1.3  The Alarm is designed for continuous 24×7 

operation  indoors  inside  terrestrial  stationary 
objects.  

1.4 Operating conditions: 

-  Ambient  air  temperature:  between  -10  and 

50

С; 

-  Relative  humidity:  up  to  95%  at  a 

temperature 35

С; 

     -  Atmospheric  pressure:  between  84  and 
107 kPa. 

 

2   SPECIFICATIONS 

2.1

 

Main technical data: 

- Sensitivity: not less than  0.05 dB/m; 

- Technical availability time: 
    not more than 15 seconds;

 

- Power supply voltage: 3V; 
- Current consumption: not more than 2 µA; 
-  Sound  volume  level  at  a  distance  of  3  m:  not 

less than 85 dB;

 

- Maximum number of Alarms in a group: not 

more than 32; 

- Overall dimensions:  
diameter – not more than 105 mm, 

 

    height – not more than 59 mm.

 

2.2  Alarm  triggering  is  confirmed  by  an 

audible signal and built-in LED flashing. 

2.3  The  output  signal  of  triggered  Alarm  is 

not  saved  after  the  moment  when  the  effects  of 
the combustion products complete.  

2.4  Alarm weight including a socket, kg: not 

more than 0.15. 

3 PRODUCT STRUCTURE AND 

FUNCTIONING 

3.1  The 

Alarm 

is 

an 

automatic 

optoelectronic  device  for  audible  and  optical 
signaling  when  the  smoke  density  in  its  location 
exceeds the threshold value. 

3.2  The  Alarm  appears  as  a  structure 

consisted  of  the  Alarm  itself  and  a  base.  The 
Alarm is connected to the base with a lock.  

Summary of Contents for CV212-12

Page 1: ...С Atmospheric pressure between 84 and 107 kPa 2 SPECIFICATIONS 2 1 Main technical data Sensitivity not less than 0 05 dB m Technical availability time not more than 15 seconds Power supply voltage 3V Current consumption not more than 2 µA Sound volume level at a distance of 3 m not less than 85 dB Maximum number of Alarms in a group not more than 32 Overall dimensions diameter not more than 105 mm...

Page 2: ... Alarm shall be carried out by power tool with an operating voltage up to 42 V and a power up to 40 W having proper insulation of live circuits from the housing of the power tool 4 3 Installation replacement and de installation of the Alarm shall be carried out observing the work at height regulation 5 PRODUCT SETUP AND INSTALLATION 5 1 The Alarm shall be installed on the monitored object in accor...

Page 3: ...indicator is flashing once every 6 minutes 6 2 Test mode Press and hold the Тест Test button until the audible signal sounds and LED indication flashes then release the button After a short time the audible signal terminates 6 3 Fire mode After the smoke level exceeds the acceptable value the Alarm is switched to a Pre alarm mode LED indicator flashes frequently next the Alarm is switched to a Fir...

Page 4: ...eration of Alarm group cause triggering of any one Alarm In triggered Alarm an intermittent audible signal activates as well as frequent flashing of the optical indicator All other Alarms must issue only audible signals 8 MAINTENANCE 8 1 At least once every 6 months purge the Alarm by air during 1 minute from all directions using for this purpose a vacuum cleaner or a compressor with a pressure of...