NAC Wiring
At the lower right corner of the main board the terminal blocks TB12 and TB13 are used for the
connection of notification appliances. Four individual NACs marked 1 through 4 are provided
and the polarity shown is when the NAC is activated.
NAC 3
NAC 1,2
Faraday
P/N 10807
24K 1/2W
See Typical
Wiring
Use the following table to configure the NACs for either Class A or Class B operation.
NAC #s
Class “B”
Operation
Paired Class
“A” Operation
1,2 JP1 JP2
3,4 JP3 JP4
NAC Rating:
Alarm Voltage: 24V FW regulated (nominal)
Max. Alarm Current: 1.5A/NAC circuit
Max. Ripple: 16VAC
Max. Wire Voltage Drop: 1.0VDC
Max. Standby Current: 1.0mA
NOTE:
The maximum total current for the MPC-6000
NACs is 3.0A and 6.0A with the optional
additional Transformer P/N NPE-1.
The maximum total current for the MPC-7000
NACs is 5.0A and 8.0A with the optional
additional Transformer P/N NPE-1.
Typical
Notification Appliance Circuit
Style Z, Class A
Supervised, Power Limited
See Appendix B for
Compatible Devices
No EOL Device
Typical
Notification Appliance Circuit
Style Y, Class B
Supervised, Power Limited
See Appendix B for
Compatible Devices
See table for NAC Jumper
Configurations
Polarity Shown
In Activated Condition
P/N 140-820405
24K ½W