MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
24
MPC-6000 / MPC-7000 / RND-2 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the
Alarm
LED flashes, LCD displays alarm condition and the panel buzzer sounds
steady. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel
are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic
signal has been received at the Fire Department.
Authorized Personnel Only
To acknowledge the alarm:
To acknowledge the alarm, press the
Acknowledge
button. The local buzzer will be silenced and
the
Alarm
LED will change from on-flashing to on-steady.
Note: The alarm may only be acknowledged at the node which initiates the alarm or the
RND-2.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted
,
press the
Alarm Silenced
button. The silenceable notification appliances will be silenced. The
Alarm Silenced
LED will be
on-steady.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a
predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing
the
System Reset
switch.
Trouble Operation
Trouble is indicated by:
Trouble
LED flashes
LCD will display trouble conditions
Panel buzzer sounds on-pulsing
To acknowledge the trouble:
Press the
Acknowledge
button
.
The
Trouble
LED turns on-steady and the buzzer turns off. When
the trouble condition has been cleared, you may need to reset the panel to restore to a normal
standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to
initiate a fire alarm sequence.
Normal Standby Condition
The green
AC Power On
LED will be lit and no other indicators on
.