EDA-R6030 Installation Manual 

 

Page 

1

 of 6                                      Ref: EDA_R6030_install_V107.doc    

 

Electro-Detectors

 

  Zerio Plus

 

EDA-R6030 Radio Combined Optical Smoke Detector and Sounder 

 With LED Beacon Installation Instructions 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
The EDA-R6030 Radio Combined Optical Smoke Detector and Sounder with LED Beacon is used as part of the Zerio 
Plus Radio Fire Alarm System.  It cannot be used with other ranges of Electro-Detectors products. 
 
It should be noted that there is no EN54 standard for battery operated sounders and beacons for fire alarm systems and 
therefore there is no need to achieve compliance, however the unit has been designed and measured to conform with the 
relevant parts of EN54 part 3 and part 23. This unit has been tested by an EN54 accredited test house to EN54-3. 
 
The unit is rated to IP21C and should only be used for indoor use. 
 

To fix the base to the ceiling 

The smoke detector should be fitted in an appropriate position as detailed in BS5839 Part 1. The base plate should be 
separated from the unit by rotating the detector anti-clockwise and pulling apart. The base should be screwed to a flat 
surface  using  2  x  No  6  screws  of  appropriate  length  for  the  material  that  the  unit  is  being  mounted  on.  It  is 
recommended  that  the  base  should  be  used  as  a  template  for  the  screw  holes.  If  the  surface  is  not  flat,  the  unit  may 
buckle  and  cause  tamper  conditions,  when  screwed  tightly  to  the  surface.  It  is  recommended  that  the  units  not  be 
secured too tightly or a mounting plate be fixed to the wall first. The units should not be fitted covering holes in ceilings 
where water could possibly drip through. Any hole should be made good prior to installing the detector. The unit should 
be fitted away from any metal objects or electrical items to avoid radio interference and a radio survey for the position 
should have been carried out prior to installation.  
 

Adding the device to the system 

Before the unit will operate on a system, it must be programmed via the control panel.  To program the unit the panel 
must be set in the appropriate mode to add a device to the system. If a device is being added or replaced on the system 
then the appropriate menu option should be selected on the control panel. Please refer to the panel manual for further 
information.  Before adding/replacing the device on the system you will need to know what unit number/address the unit 
is  to  be  programmed  to.    The  zone  number,  sensitivity,  volume,  area  and  text  location  information  should  also  be  to 
hand but this can be added/changed later. Some of this information is left at default. 
 

       

  

 

        0359 

 

Electro Detectors Ltd. 

Electro House 

Edinburgh Way 

Harlow, Essex 

CM20 2EG, UK

 

EN54-3:2001+A1:2002+A2:2006 
EN54-7:2000+A1:2002+A2:2006 
EN54-25:2008 
 
0359-CPR-00231 (2014) 
DOP_EDA_R6030 

 
 
EDA-R6030

  

Radio combined smoke detector 
and sounder with beacon for use 
in fire detection and fire alarm 
systems for buildings. 
Type A: For Indoor Use 
Category O 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Zerio Plus EDA-R6030

Page 1: ...tly to the surface It is recommended that the units not be secured too tightly or a mounting plate be fixed to the wall first The units should not be fitted covering holes in ceilings where water could possibly drip through Any hole should be made good prior to installing the detector The unit should be fitted away from any metal objects or electrical items to avoid radio interference and a radio ...

Page 2: ...ximum 80dB at 1m Medium 75dB at 1m Low 65dB at 1m Quiet Very Low Level 35dB at 1m Off No Sound 0dB type tested to this volume This was the minimum volume recorded in all directions Depending on orientation a maximum of 90dB can be achieved Area 1 and Area 2 In order to allow for sector sounding a sounder unit can be programmed in to a logical area or group eg 1st floor Usually the systems are set ...

Page 3: ...under tone number 0 and has been type approved to this Other options have not been approved Four user defined tones can be added to the system The swept tone sweeps from 1056Hz to 918Hz in 500mS The pulsed single frequency operates on a 50 duty cycle and is on for 1 second Sounder Tone Number Tone Name Tone Description Beacon 0 Swept Swept Tone ON 1 Pulsed Pulsed 1s on 1s off ON 2 Swept Swept Tone...

Page 4: ...ugh smoke enter the chamber the unit will indicate the alarm condition by illuminating the LED The internal buzzer on the detector will also beep An alarm transmission will be made to the control panel and the alarm will be indicated on the panel The sounder is instructed to sound by the control panel and so if programmed accordingly the sounder would sound a few seconds after the alarm is display...

Page 5: ... this could be caused by the batteries being flat the unit failing to operate something obstructing the radio signal path or the device not being installed correctly with an adequate signal strength Battery Fault The unit has detected a problem with the battery Unit Removal If the unit is removed from its base the panel will display a unit removal tamper fault Tx Rx Fault A failure with the transm...

Page 6: ...overs mains powered devices and does not cover battery operated devices the operational performance of the LED Beacon has not been determined for this device Please refer to Electro Detectors for advice Volumetric Light Output Shape to be advised Max Fitting Height to be advised Flash Rate 1Hz Light Output On time 6 5mS www acornfiresecurity com www acornfiresecurity com ...