EDA-R6030 Installation Manual 

 

Page 

5

 of 6                                      Ref: EDA_R6030_install_V107.doc    

 

Electro-Detectors

 

8.

 

With these buttons pressed down, fit the power link. 

9.

 

Let the unit go into its log-on mode, (it will beep) and keep the buttons pressed down. 

10.

 

After another 5 seconds a second BEEP will sound, at this point release the buttons.  This will re-set the battery 
counter after a further 15 minutes. If you realise that you didn’t want to reset the counter, then power the unit 
down by removing the power pin. Leave for 5 seconds and re-apply the power. The counter will not reset. 

11.

 

Refit the device onto its base. 

 

 
Faults displayed on the control panel from smoke detectors:- 

 

Low  Battery: 

The  batteries  are  approaching  their  end  of  life.    The  unit  will  continue  to  operate  for  a  further  60 

days in which time the batteries should be changed. 
 

Verify Fail: 

The panel has lost communication with the device, this could be caused by the batteries being flat, the 

unit failing to operate, something obstructing the radio signal path or the device not being installed correctly with an 
adequate signal strength. 
 

Battery Fault:

 The unit has detected a problem with the battery. 

 

Unit Removal: 

If the unit is removed from its base, the panel will display a unit removal/tamper fault. 

 

Tx/Rx Fault: 

A failure with the transmit / receive module of the device. It is suggested that the fault should be reset 

and if the same fault occurs within 60 minutes the unit be replaced. 
 

Int Fault:

 The unit has detected an internal problem with the way it is operating. There are several faults that can 

cause this but the usual way of solving the problem is to replace the unit or return it for repair. It is suggested that 
the fault should be reset and if the same fault occurs within 60 minutes the unit be replaced. The faults can relate to 
the  operation  of  the  sensing  head,  if  fitted,  the  micro-processor  controlling  the  device,  its  internal  memory  and  a 
host more. 
 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Zerio Plus EDA-R6030

Page 1: ...tly to the surface It is recommended that the units not be secured too tightly or a mounting plate be fixed to the wall first The units should not be fitted covering holes in ceilings where water could possibly drip through Any hole should be made good prior to installing the detector The unit should be fitted away from any metal objects or electrical items to avoid radio interference and a radio ...

Page 2: ...ximum 80dB at 1m Medium 75dB at 1m Low 65dB at 1m Quiet Very Low Level 35dB at 1m Off No Sound 0dB type tested to this volume This was the minimum volume recorded in all directions Depending on orientation a maximum of 90dB can be achieved Area 1 and Area 2 In order to allow for sector sounding a sounder unit can be programmed in to a logical area or group eg 1st floor Usually the systems are set ...

Page 3: ...under tone number 0 and has been type approved to this Other options have not been approved Four user defined tones can be added to the system The swept tone sweeps from 1056Hz to 918Hz in 500mS The pulsed single frequency operates on a 50 duty cycle and is on for 1 second Sounder Tone Number Tone Name Tone Description Beacon 0 Swept Swept Tone ON 1 Pulsed Pulsed 1s on 1s off ON 2 Swept Swept Tone...

Page 4: ...ugh smoke enter the chamber the unit will indicate the alarm condition by illuminating the LED The internal buzzer on the detector will also beep An alarm transmission will be made to the control panel and the alarm will be indicated on the panel The sounder is instructed to sound by the control panel and so if programmed accordingly the sounder would sound a few seconds after the alarm is display...

Page 5: ... this could be caused by the batteries being flat the unit failing to operate something obstructing the radio signal path or the device not being installed correctly with an adequate signal strength Battery Fault The unit has detected a problem with the battery Unit Removal If the unit is removed from its base the panel will display a unit removal tamper fault Tx Rx Fault A failure with the transm...

Page 6: ...overs mains powered devices and does not cover battery operated devices the operational performance of the LED Beacon has not been determined for this device Please refer to Electro Detectors for advice Volumetric Light Output Shape to be advised Max Fitting Height to be advised Flash Rate 1Hz Light Output On time 6 5mS www acornfiresecurity com www acornfiresecurity com ...

Reviews: